Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 385
5.11.12
Fault code output selection
When a fault occurs, the corresponding data can be output as a 4-bit digital signal using via an open
collector output terminal.
The fault code can be read using an input module of programmable controller, etc.
●
Fault codes can be output to the output terminals by setting Pr. 76 "Fault code output selection"
= "1 or 2".
●
When the setting is "2", a fault code is only output when a fault occurs. In normal operation the
terminal outputs the signal assigned in Pr. 191 to Pr. 194 (output terminal function selection).
●
The fault codes that can be output are shown in the table below.
(0: Output transistor OFF, 1: Output transistor ON)
When Pr. 76 = "2", the terminal outputs the signal assigned by Pr. 191 to Pr. 194.
Pr.
Name
Initial value
Setting range
Description
76
M510
Fault code output selection
0
0
Without fault code output
1
With fault code output
(Refer to the table below.)
2
Fault code is output only when a fault
occurs.
(Refer to the table below.)
Operation panel
indication (FR-DU08)
Output terminal operation
Fault code
SU
IPF
OL
FU
0
0
0
0
0
E.OC1
0
0
0
1
1
E.OC2
0
0
1
0
2
E.OC3
0
0
1
1
3
E.OV1 to E.OV3
0
1
0
0
4
E.THM
0
1
0
1
5
E.THT
0
1
1
0
6
E.IPF
0
1
1
1
7
E.UVT
1
0
0
0
8
E.FIN
1
0
0
1
9
E.BE
1
0
1
0
A
E. GF
1
0
1
1
B
E.OHT
1
1
0
0
C
E.OLT
1
1
0
1
D
E.OPT
E.OP1
1
1
1
0
E
Other than the above
1
1
1
1
F
Tab. 5-147:
Alarm codes
NOTE
If an error occurs while Pr. 76 ≠ "0", the output terminals SU, IPF, OL, and FU output the signals in
the table above regardless of the settings in Pr. 191 to Pr. 194 (output terminal function selection).
Take caution when controlling the inverter with the output signals set by Pr. 191 to Pr. 194.
Parameters referred to
Pr. 190 to Pr. 196
(output terminal function selection)
=>
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......