(D) Operation command and frequency command
Parameters
5 - 270
Switching operation mode by external signal (X16 signal)
●
When External operation and the operation from the operation panel are used together, the PU
operation mode and External operation mode can be switched during a stop (during motor stop,
start command OFF) by using the PU-External operation switchover signal (X16).
●
When Pr. 79 = "0", "6" or "7", switching between the PU operation mode and External operation
mode is possible. (When Pr. 79 = "6", the switchover can also be made during operation.)
●
To input the X16 signal, set "16" in any of Pr. 178 to Pr. 189 (input terminal function selection) to
assign the function to a terminal.
Switching the operation mode by external signals (X65, X66 signals)
●
When Pr. 79 = "0, 2 or 6", the PU operation mode and External operation mode can be changed to
the Network operation mode during a stop (during motor stop, start command OFF) by the PU/
NET operation switchover (X65) signal, the External/NET operation switchover (X66) signal. (When
Pr. 79 = "6", switchover is enabled during operation.)
●
To switch between the Network operation mode and the PU operation mode
Set Pr. 79 = "0 (initial value) or 6".
Set Pr. 340 "Communication startup mode selection" = "10 or 12".
Set "65" in any of Pr. 178 to Pr. 189 to assign the NET-PU operation switching signal(X65) to a
terminal.
#
When the X65 signal is ON, the PU operation mode is selected. When the X65 signal is OFF, the
Network operation mode is selected.
Pr. 79
setting
X16 signal status and operation
mode
Remarks
ON (External)
OFF (PU)
0 (initial value)
External
operation mode
PU operation
mode
Switching among the External, PU, and NET operation modes
is enabled.
1
PU operation mode
PU operation mode fixed
2
External operation mode
External operation mode fixed. (Switching to NET operation
mode is enabled.)
3, 4
External/PU combined operation
mode
External/PU combined operation mode fixed
6
External
operation mode
PU operation
mode
Switching among the External, PU, and NET operation mode
is enabled while running.
7
X12 (MRS)
ON
External
operation mode
PU operation
mode
Switching among the External, PU, and NET operation mode
is enabled. (In the External operation mode, output shutoff.)
X12 (MRS)
OFF
External operation mode
External operation mode fixed. (Forcibly switched to External
operation mode.)
Tab. 5-104:
Operation mode switching by signal X16
NOTES
The status of the operation mode follows the Pr. 340 "Communication startup mode selection"
setting and the ON/OFF state of the X65 and X66 signals. (For details, refer to page 5-270.)
The priority among Pr. 79 and Pr. 340 and signals is Pr. 79 > X12 > X66 > X65 > X16 > Pr. 340.
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may
affect the other functions. Set parameters after confirming the function of each terminal.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......