For customers replacing the conventional model with this inverter
Appendix
A - 2
Installation precautions
●
Removal procedure of the front cover is different. (Refer to page 2-7.)
●
Plug-in options of the FR-A700 series are not compatible.
●
Operation panel (FR-DU07) cannot be used.
Wiring precautions
The spring clamp type terminal block has changed to the screw type. Use of blade terminals is rec-
ommended.
Instructions for continuous use of the FR-PU07 (parameter unit)
●
For the FR-A800 series, many functions (parameters) have been added. When setting these
parameters, the parameter names and setting ranges are not displayed.
●
Only the parameter with the numbers up to "999" can be read and set. The parameters with the
numbers after "999" cannot be read or set.
●
Many protective functions have been added for the FR-A800 series. These functions are available,
but all faults are displayed as "Fault". When the faults history is checked, "ERR" appears. Added
faults will not appear on the parameter unit. (However, MT1 to MT3 are displayed as MT.)
●
Parameter copy/verification function are not available.
Copying parameter settings
The FR-A700 series' parameter settings can be easily copied to the FR-A800 series by using the setup
software (FR Configurator2). (Not supported by the setup software FR-SW3-SETUP or older.)
PU
앫
FR-DU07 (4-digit LED)
앫
FR-PU07
앫
FR-DU08 (5-digit LED)
앫
FR-LU08 (LCD operation panel)
앫
FR-PU07 (Some functions, such as
parameter copy, are unavailable.)
앫
FR-DU07 is not supported.
Plug-in option
Dedicated plug-in options (not interchangeable)
Communication option
Connected to the connector 3
Connected to the connector 1
Installation size
앫
For standard models, installation size is compatible for all capacities.
(Replacement between the same capacities does not require new mounting holes.)
앫
For separated converter types, installation size is not compatible. (New mounting
holes are required.)
Converter
Built-in for all capacities
An optional converter unit (FR-CC2) is
required for separated converter types.
DC reactor
The 75K or higher comes with a DC reactor
(FR-HEL).
For the FR-A820-03800(75K) or higher, the
FRA840-02160(75K) or higher, and when a
75 kW or higher motor is used, select a DC
reactor suitable for the applicable motor
capacity. (A DC reactor is not included.)
Separated converter types (converter unit
FR-CC2) and IP55 compatible models have
a built-in DC reactor.
Item
FR-A700
FR-A800
Tab. A-1:
Differences between FR-A700 and FR-A800 (2)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......