Parameters
Speed control under Real sensorless vector control, vector control, PM sensorless vector control
FR-A800
5 - 85
When changing from V/F control or Advanced magnetic flux vector control to Real sensorless
vector control or vector control in FR-A820-00250(3.7K) or lower or FR-A840-00126(3.7K) or lower,
150% changes to 200%.
813
H702
Torque limit level (3rd
quadrant)
9999
0 to 400%
Set the torque limit level for reverse rotation power
driving.
9999
Limit using Pr. 22 or the analog terminal values.
814
H703
Torque limit level (4th
quadrant)
9999
0 to 400%
Set the torque limit level for reverse rotation
regenerative driving.
9999
Limit using Pr. 22 or the analog terminal values.
815
H710
Torque limit level 2
9999
0 to 400%
When the torque limit selection (TL) signal is ON,
Pr. 815 is the torque limit value regardless of Pr. 810.
9999
The torque limit selected in Pr. 810 is valid.
816
H720
Torque limit level during
acceleration
9999
0 to 400%
Set the torque limit value during acceleration.
9999
The same torque limit as constant speed.
817
H721
Torque limit level during
deceleration
9999
0 to 400%
Set the torque limit value during deceleration.
9999
The same torque limit as constant speed.
858
T040
Terminal 4 function
assignment
0
0, 1, 4, 9999
The torque limit level can be changed with setting
value "4" and the signal to terminal 4.
868
T010
Terminal 1 function
assignment
0
0 to 6, 9999
The torque limit level can be changed with setting
value "4" and the signal to terminal 1.
874
H730
OLT level setting
150%
0 to 400%
A trip can be set for when the torque limit is activated
and the motor stalls. Set the output at which to
activate the trip.
NOTES
The lower limit for the torque limit level under Real sensorless vector control is set to 30% even if a
value lower than 30% is set.
When the low-speed range high-torque characteristic is disabled under PM sensorless vector con-
trol (Pr. 788 = "0"), the torque limit is not activated in a low-speed range with a rated frequency of
less than 10%.
Under PM sensorless vector control, the torque limit level is reduced inversely proportional to the
output frequency in the constant output range of the rated motor frequency or higher.
Pr.
Name
Initial
value
Setting
range
Description
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......