Parameters
(E) Environment setting parameters
FR-A800
5 - 223
●
The life alarm signal (Y90) turns ON when any of the control circuit capacitor, main circuit capacitor,
cooling fan, inrush current limit circuit, or internal air circulation fans reaches the life alarm output
level.
●
For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of
Pr. 190 to Pr. 196 (output terminal function selection).
Life display of the inrush current limit circuit (Pr. 256)
(Standard models and IP55 compatible models)
●
The life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in Pr. 256.
●
The number of contact (relay, contactor, thyristor) ON times is counted, and it is counted down
from 100% (0 time) every 1%/10,000 times. As soon as 10% (900,000 times) is reached, Pr. 255 bit
3 is turned ON and also a warning is output to the Y90 signal.
Pr. 255
bit3
bit2
bit1
bit0
Pr. 255
bit4
bit3
bit2
bit1
bit0
Decimal
Binary
Deci-
mal
Binary
15
1111
31
1111
14
1110
×
30
1110
×
13
1101
×
29
1101
×
12
1100
×
×
28
1100
×
×
11
1011
×
27
1011
×
10
1010
×
×
26
1010
×
×
9
1001
×
×
25
1001
×
×
8
1000
×
×
×
24
1000
×
×
×
7
0111
×
23
0111
×
6
0110
×
×
22
0110
×
×
5
0101
×
×
21
0101
×
×
4
0100
×
×
×
20
0100
×
×
×
3
0011
×
×
19
0011
×
×
2
0010
×
×
×
18
0010
×
×
×
1
0001
×
×
×
17
0001
×
×
×
0
0000
×
×
×
×
16
0000
×
×
×
×
: With warnings, ×: Without warnings
Tab. 5-90:
Displaying the end of service life by bits
NOTES
When using an option (FR-A8AY, FR-A8AR, FR-A8NC, FR-A8NCE), the life can be output separately
to the control circuit capacitor life signal (Y86), main circuit capacitor life signal (Y87), cooling fan
life signal (Y88), and inrush current limit circuit life signal (Y89).
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......