Parameters
(G) Control parameters
FR-A800
5 - 697
Limiting the frequency after the droop compensation (0 limit)
By setting Pr. 288 at the time of Real sensorless vector control, vector control, or PM sensorless control,
the negative frequency command when the frequency after droop compensation can be limited.
During Advanced magnetic flux vector control, the action same as the "0" setting will be per-
formed.
Droop control break point setting (Pr. 994, Pr. 995)
By setting Pr. 994 and Pr. 995, break point (1 point) can be set up for the droop compensation fre-
quency. Setting a break point allows the inverter to raise the droop compensation frequency for light-
load (no load) operation without raising it for heavy-load operation.
Pr. 288
Setting
Operation
When the droop compensation frequency is
negative
Droop compensation
reference
0
(initial value) Without droop control during
acceleration/deceleration
Limit with 0 Hz
(Limit with 0.5 Hz under Advanced magnetic
flux vector control)
Rated motor frequency
Motor speed
Constantly droop control during
operation
Rated motor frequency
Motor speed
Constantly droop control during
operation
Do not limit (reverse)
(At the time of vector control, PM sensorless
vector control)
Rated motor frequency
Limit with 0 Hz
(At the time of Real sensorless vector control)
Tab. 5-316:
Setting of parameter 288
I002759E
Fig. 5-348:
Setting a break point for droop control
NOTE
Droop break point function is disabled in one of following conditions:
(Linear compensation by Pr. 286 will be performed.)
●
Pr. 995 = "100% (initial value)"
●
Pr. 286 < Pr. 994
●
Pr. 994
≤
Pr. 995 × Pr. 286 / 100%
100%
-100%
0
Increased amount of the
droop compensation
frequency
Frequency
Droop break point gain
(Pr. 994)
Droop break point torque
(Pr. 995)
Droop compensation
frequency
Rated
frequency
Droop gain
(Pr. 286)
Torque
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......