(G) Control parameters
Parameters
5 - 668
●
Inverter output shutoff timing with X74 signal
●
Since the torque will decrease at the time of magnetic flux decay output shutoff, set up so the
mechanical brake will operate.
●
Magnetic flux decay output shutoff will be canceled at the time of restart and when the Pre-
excitation/servo ON(LX) signal/External DC injection brake operation start (X13) signal is turned ON.
●
When the MC is installed on the inverter output side, set up so the MC is released after the
magnetic flux decay operation time (see below) has passed.
I002754E
Fig. 5-331:
Inverter output shutoff timing with X74 signal
Motor capacity
(Pr. 80 setting value)
2.2 kW or
lower
3.7 kW to
11 kW
15 kW to 30 kW 37 kW to 55 kW
75 kW or
higher
Magnetic flux decay process time
250 ms
500 ms
800 ms
900 ms
1100 ms
Tab. 5-305:
Magnetic flux decay operation time
NOTES
When operating in anything other than the Real sensorless vector control, the inverter will imme-
diately shutoff the output when the X74 signal is turned ON.
Even at the time of Real sensorless vector control, the inverter will immediately shutoff the output
when the X74 signal is turned ON during the automatic restart after instantaneous power failure
and online auto tuning during the start up.
When other output shutoff trigger (inverter fault, turning ON the MRS signal, etc.) occurs during
the magnetic flux decay operation, the magnetic flux operation is terminated, and the output is
shut off immediately.
Unlike the MRS signal, voltage is output during the magnetic flux decay output shutoff operation,
so take caution on electric shocks.
When the release timing of the mechanical brake is too fast, the motor shaft may be rotated by
dropping or external force. When the release timing is too late, the overcurrent prevention opera-
tion or electronic thermal O/L relay may operate, so perform release of the mechanical brake
matching the equipment utilizing the output frequency detection (FU) signal and output current
detection (Y12) signal.
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may
affect the other functions. Set parameters after confirming the function of each terminal.
X74
MRS
* Maximum time for the magnetic flux decay operation
X74 signal
MRS signal
Magnetic flux decay
processing time*
Do not turn off MC
during this processing time
MC on the output side
Mechanical brake
Output voltage
Output voltage
Mechanical brake
MC on the output side
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
RUN
RUN
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......