Protective functions
Causes and corrective actions
FR-A800
6 - 21
Operation panel
indication
E.OV2
FR-LU-08
OV During Cnst Spd
Name
Regenerative overvoltage trip during constant speed
Description
If regenerative power causes the inverter's internal main circuit DC voltage to reach or exceed
the specified value, the protection circuit is activated to stop the inverter output. The circuit may
also be activated by a surge voltage produced in the power supply system.
Check point
앫
Check for sudden load change.
앫
Check that the Pr. 22 "Stall prevention operation level" is not set to the no load current or
lower.
앫
Check if the stall prevention operation is frequently activated in an application with a large
load inertia.
앫
Check that acceleration/deceleration time is not too short.
Corrective action
앫
Keep the load stable.
앫
Use the regeneration avoidance function (Pr. 882 to Pr. 886). (Refer to page 5-685.)
앫
Use the brake unit or power regeneration common converter (FR-CV) as required.
앫
Set a value larger than the no load current in Pr. 22.
앫
Set Pr. 154 "Voltage reduction selection during stall prevention operation" = "10, 11".
(Refer to page 5-84.)
앫
Set the acceleration/deceleration time longer. (Under vector control or Advanced magnetic
flux vector control, the output torque can be increased. However, sudden acceleration may
cause an overshoot in speed, resulting in an occurrence of overvoltage.)
Operation panel
indication
E.OV3
FR-LU-08
OV During Dec
Name
Regenerative overvoltage trip during deceleration or stop
Description
If regenerative power causes the inverter's internal main circuit DC voltage to reach or exceed
the specified value, the protection circuit is activated to stop the inverter output. The circuit may
also be activated by a surge voltage produced in the power supply system.
Check point
앫
Check for sudden speed reduction.
앫
Check if the stall prevention operation is frequently activated in an application with a large
load inertia.
Corrective action
앫
Set the deceleration time longer. (Set the deceleration time which matches the moment of
inertia of the load.)
앫
Make the brake cycle longer.
앫
Use the regeneration avoidance function (Pr. 882 to Pr. 886). (Refer to page 5-685.)
앫
Use the brake unit or power regeneration common converter (FR-CV) as required.
앫
Set Pr. 154 "Voltage reduction selection during stall prevention operation" = "10, 11".
(Refer to page 5-84.)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......