(H) Protective function parameter
Parameters
5 - 306
5.10.7
I/O phase loss protection selection
The output phase loss protection function, which stops the inverter output if one of the three phases
(U, V, W) on the inverter's output side (load side) is lost, can be disabled.
The input phase loss protective function on the inverter input side (R/L1, S/L2, T/L3) can be enabled.
The setting is available only for standard models and IP55 compatible models.
Output phase loss protection selection (Pr. 251)
●
When Pr. 251 = "0", output phase loss (E.LF) protection is disabled.
Input phase loss protection selection (Pr. 872) (Standard models and IP55 compatible models)
When Pr. 872 = "1", input phase loss (E.ILF) protection will be activated if one of three phases is de-
tected to be lost for 1 s continuously.
Pr.
Name
Initial
value
Setting
range
Description
251
H200
Output phase loss
protection selection
1
0
Without output phase loss protection
1
With output phase loss protection
872
H201
Input phase loss
protection selection
0
0
Without input phase loss protection
1
With input phase loss protection
NOTES
When several motors are connected, output phase loss cannot be detected even if the wiring to
one motor loses phase.
If an input phase is lost while Pr. 872 = "1" (with input phase loss protection), Pr. 261 "Power failure
stop selection" ≠ "0" (power failure stop function enabled), the motor decelerates to stop without
outputting E.ILF.
In the case of R/L1, S/L2 phase loss, the input phase loss protection will not operate, and the
inverter will trip.
If an input phase loss continues for a long time, the converter section and capacitor lives of the
inverter will be shorter.
Parameters referred to
Pr. 261
Power failure stop selection
=>
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......