(G) Control parameters
Parameters
5 - 674
Make the motor perform coast to stop
●
Set the time from the time the start signal is turned OFF to when the output is shutoff in Pr. 250.
When set to "1000 to 1100", output is shutoff after (Pr. 250 – 1000) s.
●
The output is shutoff after the set time of Pr. 250 has elapsed after the start signal is turned OFF.
The motor will coast to stop.
●
The RUN signal will be turned OFF at the time of output stop.
I001144E
Fig. 5-336:
Stop operation when parameter 250 ≠ 8888 or 9999
NOTES
Stop selection is disabled when following functions are operating.
●
Position control (Pr. 419 = "0")
●
Power failure stop function (Pr. 261)
●
PU stop (Pr. 75)
●
Deceleration stop due to fault initiation (Pr. 875)
●
Deceleration stop due to communication error (Pr. 502)
●
Offline auto tuning (with motor rotation)
When Pr. 250 ≠ "9999 or 8888", acceleration/deceleration is performed in accordance to the fre-
quency command until the output is shutoff by turning OFF the start signal.
When the restart signal is turned ON during the motor coasting, the operation is resumed from
Pr. 13 "Starting frequency".
Even with the setting of coasting to stop, when the LX signal is turned ON, the motor does not
coast but zero speed control or servo lock is applied.
Parameters referred to
Pr. 7
Acceleration time
=>
Pr. 8
Deceleration time
=>
Pr. 13
Starting frequency
=>
Pr. 75
Reset selection/disconnected PU detection/PU stop selection
=>
Pr. 261
Power failure stop selection
=>
Pr. 502
Stop mode selection at communication error
=>
Pr. 875
Fault definition
=>
Output
frequency [Hz]
Start signal
Motor coasts to stop
Output is shut off when set time elapses after
start signal turns OFF
Time
ON
ON
OFF
OFF
RUN signal
Pr. 250
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......