(D) Operation command and frequency command
Parameters
5 - 272
5.9.2
Startup in Network operation mode at power-ON
When power is switched ON or when power comes back ON after an instantaneous power failure, the
inverter can be started up in the Network operation mode. After the inverter starts up in the Network
operation mode, parameter writing and operation can be commanded from programs.
Set this mode when performing communication operation using the RS-485 terminals or a commu-
nication option.
NOTES
The priority of Pr. 79 and Pr. 340 and signals is Pr. 79 > X12 > X66 > X65 > X16 > Pr. 340.
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may
affect the other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 15
Jog frequency
=>
Pr. 4 to Pr. 6, Pr. 24 to 27,
Pr. 232 to Pr. 239
(multi-speed operation)
=>
Pr. 75
Reset selection/disconnected PU detection/PU stop selection
=>
Pr. 161
Frequency setting/key lock operation selection
=>
Pr. 178 to Pr. 182
(input terminal function selection)
=>
Pr. 190 to Pr. 196
(output terminal function selection)
=>
Pr. 340
Communication startup mode selection
=>
Pr. 550
NET mode operation command source selection
=>
Pr.
Name
Initial
value
Setting
range
Description
79
D000
Operation mode selection
0
0 to 4, 6, 7
Selects the operation mode.
(Refer to page 5-263.)
340
D001
Communication startup mode
selection
0
0
Follows the Pr. 79 setting.
1,2
The inverter starts up in the Network operation
mode.
If an instantaneous power failure occurs when
"2" is set, the operating status before the
instantaneous power failure is maintained.
10,12
The inverter starts up in the Network operation
mode. The operation mode can be changed
between the PU operation mode and Network
operation mode from the operation panel.
If an instantaneous power failure occurs when
"12" is set, running is continued at the
condition before the instantaneous power
failure.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......