Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 367
Adjusting the output terminal response level (Pr. 289)
The response level of the output terminals can be delayed in a range of 5 to 50 ms. (Operation example
for the RUN signal.)
Inverter operation ready signals (RY, RY2 signals)
and inverter running signals (RUN, RUN2, RUN3 signals)
●
Operation under V/F control and Advanced magnetic flux vector control
–
When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON
(stays ON during operation.)
–
When the inverter output frequency reaches Pr. 13 "Starting frequency" or higher, the Inverter
running (RUN, RUN2) signals turn ON. The signal is OFF while the inverter is stopped and during
DC injection brake operation. Inverter
–
The Inverter running and start command is ON (RUN3) signal is ON while the inverter is running
or the start signal is ON. (When the start command is ON, the RUN3 signal output turns ON
even while the inverter's protective function is activated or the MRS is ON.) During DC injection
brake operation as well, the output is ON, and when the inverter stops, it turns OFF.
Fig. 5-164:
Adjusting the RUN signal response level
I002620E
NOTES
When Pr. 157 "OL signal output timer" is set for the Overload warning (OL) signal output, the OL
signal is output when the set time of (Pr. 157 + Pr. 289) elapses.
For the output signal and the fault code output (on page 5-382) used in the PLC function (on page
5-587), the Pr. 289 setting is invalid (no filter).
I002621E
Fig. 5-165:
Ready and motor running signals
RUN
Pr. 289 ≠ 9999
Pr. 289
Pr. 289
OFF
OFF
ON
ON
Time
RUN
Pr. 289 = 9999
Output fr
equen
cy
STF
RH
RY
RUN3
RUN
(RUN2)
Pr. 13
Reset
processing
Power supply
DC injection brake
operation point
DC injection
brake
operation
Time
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
Ou
tput fr
equenc
y
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......