Parameters
(A) Application parameters
FR-A800
5 - 563
Automatic restart after instantaneous power failure function
●
The inverter output is shut off at the activation of the instantaneous power failure protection
(E.IPF) or undervoltage protection (E.UVT). (Refer to page 6-9 for E.IPF or E.UVT.)
●
When E.IPF or E.UVT is activated, the instantaneous power failure (IPF)/undervoltage signal is
output.
●
The IPF signal is assigned to terminal IPF in the initial setting. To assign the IPF signal to a different
terminal, set "2 (positive logic) or 102 (negative logic)" to any of Pr. 190 to Pr. 196 (Output terminal
function selection).
●
When the automatic restart after instantaneous power failure function is selected, motor restarts
at the power restoration after an instantaneous power failure or undervoltage. (E.IPF and E.UVT
are not activated.)
Connection (CS signal)
●
Restart is enabled at turn-ON of the automatic restart after instantaneous power failure/flying
start (CS) signal.
●
The inverter operation is disabled at turn-OFF of the CS signal while Pr. 57 "Restart coasting time"
≠
"9999" (with restart).
NOTES
To operate the inverter with the automatic restart after instantaneous power failure function ena-
bled, check the following points.
Set Pr. 57 "Restart coasting time" = "0".
Turn the terminal CS (Selection of automatic restart after instantaneous power failure, flying start)
ON.
Fig. 5-280:
IPF signal
I001353E
I002849E
Fig. 5-281:
Connection example
15 ms to 100 ms*
Power
supply
ON
OFF
OFF
ON
* 10 to 100 ms for IP55 compatible models
STF
IM
MCCB
CS
SD
CS
SD
S1/L21
R1/L11
T/L3
S/L2
R/L1
MC1
MC2
W
V
U
MC3
MC
switchover
sequence
For use for only automatic
restart after instantaneous
power failure or flying start,
turn ON the CS signal in
advance.
With electronic bypass sequence
Only with restart after instantaneous power failure
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......