(C) Motor constant parameters
Parameters
5 - 464
●
Set a given value as the motor constant parameter. The displayed increments of the read motor
constants can be changed with Pr. 684 "Tuning data unit switchover".
For the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
For the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
First
motor
Pr.
Second
motor
Pr.
Name
Pr. 684 = 0 (initial value)
Pr. 684 = 1
Initial
value
Setting
range
Setting in-
crements
Range indication
Unit
indication
90
458
Motor constant (R1)
0 to ***,
9999
1
0 to 50 Ω, 9999
0.001 Ω
9999
0 to 400 mΩ, 9999
0.01 mΩ
92
460
Motor constant (L1)/
d-shaft inductance
(Ld)
0 to 500 mH, 9999
0.01 mH
0 to 50 mH, 9999
93
461
Motor constant (L2)/
q-shaft inductance
(Lq)
0 to 500 mH, 9999
0.01 mH
0 to 50 mH, 9999
706
738
Induced voltage
constant (phi f )
0 to 5000 mV/s/rad,
9999
0.1 mV/
(rad/s)
859
860
Torque current/
Rated PM motor
current
0 to 500 A, 9999
0 to 3600 A, 9999
0.1 A
Tab. 5-195:
Parameter setting ranges
NOTES
As the motor constants measured in the offline auto tuning have been converted into internal
data (****), refer to the following setting example when making setting:
Setting example:
To slightly increase Pr. 90 value (5%)
If Pr. 90 = "2516" is displayed
The value can be calculated with "2516 × 1.05 = 2641.8". Therefore set Pr. 90 = "2642".
(The value displayed has been converted into a value for internal use. Hence, simple addition of a
given value to the displayed value has no significance)
Setting "9999" disables the tuning data. The MM-CF constant is used for the IPM motor MM-CF,
and the inverter internal constant is used for a PM motor other than MM-CF.
Parameters referred to
Pr. 9
Electronic thermal O/L relay
=>
Pr. 71
Applied motor
=>
Pr. 178 to Pr. 189
(input terminal function selection)
=>
Pr. 800
Control method selection
=>
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......