(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Parameters
5 - 260
5.8.7 Lift
operation
(automatic acceleration/deceleration)
The inverter can be operated according to the load pattern of the lift with counterweight.
The setting range for the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
The setting range for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
Lift operation (Pr. 292 = "5, 6")
●
When Pr. 292 "Automatic acceleration/deceleration" is set to "5" or "6", the lift operation is selected,
and each setting is changed, as shown in the table below.
●
During power driving, sufficient torque is generated, and during regenerative driving and during
driving with no load, the torque boost setting is adjusted automatically so as not to activate the
overcurrent protective function by overexcitation.
Pr.
Name
Initial
value
Setting range
Description
292
F500
Automatic acceleration/
deceleration
0
0
Normal operation
1
Shortest acceleration/
deceleration (without brakes)
(Refer to
page 5-
255.)
11
Shortest acceleration/
deceleration (with brakes)
3
Optimum acceleration/
deceleration
5
Lift operation 1 (stall prevention operation
level 150%)
6
Lift operation 2 (stall prevention operation
level 180%)
7, 8
Brake sequence 1, 2 (Refer to page 5-484.)
61
F510
Reference current
9999
0 to 500 A
Set the reference current during shortest
(optimum) acceleration/deceleration.
0 to 3600 A
9999
Rated output current value reference of the
inverter
64
F520
Starting frequency for
elevator mode
9999
0 to 10 Hz
Set the starting frequency for the lift
operation.
9999
Starting frequency is 2 Hz.
Name
Normal operation
Multi-
rating
(Pr. 570)
Lift operation (Pr. 292)
5
6
Torque boost
Pr. 0 (6/4/3/2/1%)
Changes according to the output current
(as shown below)
Starting frequency
Pr. 13 (0.5 Hz)
Pr. 64 (2 Hz) Accelerate after 100 ms hold.
Base frequency voltage
Pr. 19 (9999)
220 V class (440 V class)
Stall prevention operation level
Pr. 22 (150%), etc.
0(SLD)
110%
115%
1(LD)
120%
140%
2(ND)
Initial value
150%
180%
3(HD)
200%
230%
Tab. 5-98:
Valid values in the elevator mode
V/F
V/F
V/F
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......