Protective functions
Causes and corrective actions
FR-A800
6 - 11
Operation panel
indication
rE2
Name
Parameter write error
Description
앫
Parameter copy from the operation panel to the inverter was attempted during operation.
앫
A failure has occurred at the operation panel side EEPROM while writing the copied
parameters.
앫
A failure has occurred in the USB memory device while writing the copied parameters or PLC
function project data.
Check point
앫
Check that the inverter is stopped.
Corrective action
앫
After stopping the operation, perform parameter copy again. (Refer to page 5-702.)
앫
The operation panel (FR-DU08) may be faulty. Please contact your sales representative.
앫
Perform parameter copy or PLC project data copy again.
(Refer to page 5-591 and page 5-704)
앫
The USB memory device may be faulty. Replace the USB memory device.
Operation panel
indication
rE3
Name
Parameter verification error
Description
앫
The data in the inverter are different from the data in the operation panel.
앫
A failure has occurred at the operation panel side EEPROM during parameter verification.
앫
A failure has occurred in the USB memory device during parameter verification.
앫
The data in the inverter are different from the data in the USB memory device or the
personal computer (FR Configurator2)
Check point
앫
Check the parameter setting of the source inverter against the setting of the destination
inverter.
Corrective action
앫
Continue the verification by pressing SET key.
Perform parameter verification again. (Refer to page 5-703.)
앫
The operation panel (FR-DU08) may be faulty. Please contact your sales representative.
앫
The USB memory device may be faulty. Replace the USB memory device.
앫
Verify the PLC function project data again. (Refer to page 5-591.)
Operation panel
indication
rE4
Name
Model error
Description
앫
A different model was used when parameter copy from the operation panel or parameter
verification was performed.
앫
The data in the operation panel were not correct when parameter copy from the operation
panel or parameter verification was performed.
Check point
앫
Check that the parameter copy or verification source inverter is of the same model.
앫
Check that parameter copy to the operation panel was not interrupted by switching OFF the
power or by disconnecting the operation panel.
Corrective action
앫
Perform parameter copy and parameter verification between inverters of the same model
(FR-A800 series).
앫
Perform parameter copy to the operation panel from the inverter again.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......