Parameters
(A) Application parameters
FR-A800
5 - 587
5.14.17 PLC
function
The inverter can be run in accordance with a sequence program.
In accordance with the machine specifications, a user can set various operation patterns: inverter
movements at signal inputs, signal outputs at particular inverter statuses, and monitor outputs, etc.
Pr.
Name
Initial
value
Setting
range
Description
414
A800
PLC function operation
selection
0
0
PLC function disabled
1
PLC function
enabled
The SQ signal is enabled by input from a
command source (external input
terminal/communication).
2
The SQ signal is enabled by input from
an external input terminal.
415
A801
Inverter operation lock
mode setting
0
0
The inverter start command is enabled regardless of the
operating status of the sequence program.
1
The inverter start command is enabled only while the
sequence program is running.
416
A802
Pre-scale function
selection
0
0 to 5
Unit scale
factor
0: No function
1: × 1
2: × 0.1
3: × 0.01
4: × 0.001
5: × 0.0001
When the pulse train is input from
terminal JOG, the number of sampled
pulses can be converted.
The result of conversion is stored to
SD1236.
"Number of sampled pulses"
= "input pulse value per count cycle" ×
"pre-scale setting value (Pr. 417)"
× "unit scale factor (Pr. 416)"
417
A803
Pre-scale setting value
1
0 to 32767
Pre-scale
setting value
498
A804
PLC function flash memory
clear
0
0, 9696
(0 to 9999)
0: Clears the flash memory fault display (no
operation after writing while the flash memory is
in normal operation).
Write
9696: Clears the flash memory (no operation
Write after writing during flash memory fault).
Other than 0 and 9696: Outside of the setting
range
0: Normal display
Read
1: The flash memory has not been cleared
because the PLC function is enabled.
9696: During flash memory clearing operation or
flash memory fault
1150 to
1199
A810 to
A859
User parameters 1to
User parameters 50
0
0 to 65535
Desired values can be set.
Because devices D206 to D255 used by the PLC function
can be mutually accessed, the values set to Pr. 1150 to Pr.
1199 can be used by the sequence program. The result of
performing calculation by a sequence program can also
be monitored by Pr. 1150 to Pr. 1199.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......