Installation and wiring
Control circuit
FR-A800
2 - 39
Communication
Safety stop signal
Ty
p
e
Terminal
Symbol
Terminal name
Terminal function description
Refer
to
page
RS
-4
85
⎯
PU connector
With the PU connector, communication can be made through
RS-485. (For connection on a 1:1 basis only)
앫
Conforming standard: EIA-485 (RS-485)
앫
Transmission format: Multidrop link
앫
Communication speed: 4800 to 115200 bps
앫
Overall length: 500 m
RS
-485
t
e
rm
ina
ls
TXD+
Inverter transmission
terminal
The RS-485 terminals enables the communication by RS-485.
앫
Conforming standard: EIA-485 (RS-485)
앫
Transmission format: Multidrop link
앫
Communication speed: 300 to 115200 bps
앫
Overall length: 500 m
TXD-
RXD+
Inverter reception terminal
RXD-
GND
SG
Earthing (grounding)
USB
⎯
USB A connector
앫
A connector (receptacle)
앫
A USB memory device enables
parameter copies and the trace
function.
앫
Interface:
Conforms to USB1.1
(USB2.0 full-speed
compatible)
앫
Transmission speed:
12 Mbps
USB B connector
앫
Mini B connector (receptacle)
앫
Connected to a personal computer
via USB to enable setting,
monitoring, test operations of the
inverter by FR Configurator2.
Tab. 2-15:
Communication signals
Terminal
Symbol
Terminal name
Terminal function description
Rated
specification
Refer
to
page
S1
Safety stop input
(Channel 1)
The terminals S1 and S2 are used for the safety stop
input signal for the safety relay module. The terminals S1
and S2 are used at the same time (dual channel).
Inverter output is shutoff by shortening/opening
between terminals S1 and SIC, or between S2 and SIC.
In the initial status, terminals S1 and S2 are shorted with
the terminal PC by shorting wires. The terminal SIC is
shorted with the terminal SD. Remove the shorting wires
and connect the safety relay module when using the
safety stop function.
Input resistance
4.7 k
Ω
Input current
4 to 6 mA DC
(with 24 V DC
input)
S2
Safety stop input
(Channel 2)
SIC
Safety stop input
terminal common
Common terminal for terminals S1 and S2.
⎯
SO
Safety monitor output
(open collector
output)
Indicates the safety stop input signal status.
Switched to LOW when the status is other than the
internal safety circuit failure. Switched to HIGH during
the internal safety circuit failure status.
(LOW is when the open collector output transistor is ON
(conducted). HIGH is when the transistor is OFF (not
conducted).)
Refer to the Safety stop function instruction manual
(BCN-A23228-001) when the signal is switched to HIGH
while both terminals S1 and S2 are open. (Please contact
your sales representative for the manual.)
Permissible load
24 V DC (27 V DC at
maximum), 0.1 A
(A voltage drop is
3.4 V at maximum
while the signal is
ON.)
(A voltage drop is
3.4 V at maximum
while the signal is
ON.)
SOC
Safety monitor output
common
Common terminal for terminal SO.
⎯
Tab. 2-16:
Safety stop signal
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......