Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 331
Input terminal
status
—
55
40215
Displays input terminal ON/OFF
state of the inverter. (Refer to
page 5-336 for DU display.)
Output terminal
status
—
H10
40216
Displays output terminal ON/OFF
state of the inverter. (Refer to
page 5-336 for DU display.)
Option input
terminal status
—
56
—
—
—
Displays input terminal ON/OFF
state of the digital input option
(FR-A8AX) on the DU.
(Refer to page 5-336 for details.)
Option output
terminal status
—
57
—
—
—
Displays output terminal ON/OFF
state of the digital output option
(FR-A8AY) and the relay output
option (FR-A8AR) on the DU.
(Refer to page 5-336 for details.)
Option input
terminal status 1
(for
communication)
—
—
40258
Input terminal X0 to X15 ON/OFF
state of the digital input option
(FR-A8AX) can be monitored via
RS-485 communication and the
communication option.
Option input
terminal status 2
(for communica-
tion)
—
—
H3B
40259
Input terminal DY ON/OFF state
of the digital input option
(FR-A8AX) can be monitored via
RS-485 communication and the
communication option.
Option output
terminal status 1
(for communica-
tion)
—
—
H3C
40260
Output terminal ON/OFF state of
the digital output option
(FR-A8AY) and relay output
option (FR-A8AR) can be
monitored via RS-485
communication and the
communication option.
Motor thermal
load factor
0.1%
61
H3D
40261
Displays the accumulated heat
value of the motor thermal O/L
relay.
The motor overload trip (E.THM)
occurs at 100%.
Inverter thermal
load factor
0.1%
62
H3E
40262
Displays the accumulated heat
value of the inverter thermal O/L
relay.
The inverter overload trip (E.THT)
occurs at 100%.
PTC thermistor
resistance
0.01 kΩ
64
H40
40264
Displays the PTC thermistor
resistance when Pr. 561 "PTC
thermistor protection level" ≠
9999 (voltage monitor when
Pr. 561 = 9999).
PID measured
value 2
0.1%
67
H43
40267
Displays the PID control
measured value even if PID
control operating conditions are
not satisfied while the PID
control is enabled (Pr.128 ≠ "0").
(Refer to page 5-537)
Cumulative
pulse
—
71
H47
40271
The cumulative number of
pulses is displayed (monitor
range: –32767 to 32767)
(for FR-A8AP/FR-A8APR).
Cumulative
pulse overflow
times
—
72
H48
40272
The number of the cumulative
pulse carrying-over times is
displayed (for FRA8AP/
FR-A8APR).
Cumulative
pulse (control
terminal option)
—
73
H49
40273
The cumulative number of
pulses is displayed (monitor
range: –32767 to 32767)
(for FR-A8TP).
Types of
monitor
Unit
Pr. 52,
Pr. 774 to Pr. 776,
Pr. 992
RS-485
communica-
tion dedicat-
ed monitor
(hexadeci-
mal)
MODBUS
RTU real
time
monitor
Minus (-)
display
Description
Tab. 5-126:
Monitor description list (4)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......