Parameters
(A) Application parameters
FR-A800
5 - 531
Selection of deviation value, measured value and set point input method, and PID action
method (Pr. 128, Pr. 609, Pr. 610)
●
Using Pr. 128, select the input method for the PID set point, measured value detected by the meter,
and externally calculated deviation. Also, select forward or reverse action.
●
Switch the power voltage/current specifications of terminals 2 and 4 by Pr. 73 "Analog input
selection" or Pr. 267 "Terminal 4 input selection" to match the specification of the input device.
After changing the Pr. 73 and Pr. 267 settings, check the voltage/current input selection switch.
Incorrect setting may cause a fault, failure or malfunction. (Refer to page page 5-389 for the
setting.)
When Pr. 133
≠
"9999", the Pr. 133 setting is valid.
For the details of CC-Link communication, refer to the Instruction Manual of the option FR-A8NC,
FR-A8NCE.
For the details of the PLC function, refer to the PLC Function Programming Manual.
Pr. 128
setting
Pr. 609
Pr. 610
PID action
Set point input
Measured value input
Deviation input
0
Invalid
PID invalid
⎯
⎯
⎯
10
Reverse action
⎯
⎯
Terminal 1
11
Forward action
20
Reverse action
Terminal 4
⎯
21
Forward action
40 to 43
Valid
Dancer control
For details on dancer control, refer to page 5-552.
50
Invalid
Reverse action
⎯
⎯
CC-Link communication
51
Forward action
60
Reverse action
⎯
61
Forward action
70
Reverse action
⎯
⎯
PLC function
(with frequency
reflected)
71
Forward action
80
Reverse action
PLC function
(with frequency
reflected)
PLC function
(with frequency
reflected)
⎯
81
Forward action
90
Reverse action
⎯
⎯
PLC function
(without frequency
reflected)
91
Forward action
100
Reverse action
PLC function
(without frequency
reflected)
PLC function
(without frequency
reflected)
⎯
101
Forward action
1000
Valid
Reverse action
According to Pr. 609
According to Pr. 610
⎯
1001
Forward action
1010
Reverse action
⎯
⎯
According to Pr. 609
1011
Forward action
2000
Reverse action
(without frequency
reflected)
According to Pr. 609
According to Pr. 610
⎯
2001
Forward action
(without frequency
reflected)
2010
Reverse action
(without frequency
reflected)
⎯
⎯
According to Pr. 609
2011
Forward action
(without frequency
reflected)
Tab. 5-219:
Related parameters
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......