Parameters
(N) Operation via communication and its settings
FR-A800
5 - 645
●
Faults history
●
Model information monitor
Pr. 343 "Communication error count"
The communication error occurrence count can be checked.
Register
Definition
Read/Write
Remarks
40501
Faults history 1
Read/Write
Data is 2 bytes and so is stored in "H00
".
The lowest 1 byte can be referred to for the error code.
(For details on error codes, refer to page 6-5.)
The faults history is batch-cleared by writing to register
40501.
Set any value for the data.
40502
Faults history 2
Read
40503
Faults history 3
Read
40504
Faults history 4
Read
40505
Faults history 5
Read
40506
Faults history 6
Read
40507
Faults history 7
Read
40508
Faults history 8
Read
Tab. 5-297:
Faults history
Register
Definition
Read/Write
Remarks
44001
Model (First and second characters)
Read
Reading inverter type in ASCII code.
"H20" (blank code) is set for blank area.
Example of FR-A840-1 (FM type)
H46, H52, H2D, H41, H38, H34, H30, H2D,
H31, H20......H20
44002
Model (Third and fourth characters)
Read
44003
Model (Fifth and sixth characters)
Read
44004
Model (Seventh and eighth characters)
Read
44005
Model (Ninth and tenth characters)
Read
44006
Model (Eleventh and twelfth characters)
Read
44007
Model (Thirteenth and fourteenth characters)
Read
44008
Model (Fifteenth and sixteenth characters)
Read
44009
Model (Seventeenth and eighteenth characters)
Read
44010
Model (Nineteenth and twentieth characters)
Read
44011
Capacity (First and second characters)
Read
Reading inverter capacity in ASCII code.
Data is read in increments of 0.1 kW, and
rounds down to 0.01 kW increments.
"H20" (blank code) is set for blank area.
Example:
0.75K ............"7"
(H20, H20, H20, H20, H20, H37)
44012
Capacity (Third and fourth characters)
Read
44013
Capacity (Fifth and sixth characters)
Read
Tab. 5-298:
Inverter type monitor
NOTE
When a 32-bit parameter setting or monitored value is read and the read value exceeds HFFFF, the
reply data will be HFFFF.
Parameter
Setting range
Minimum setting range
Initial value
343
(Read only)
1
0
Tab. 5-299:
Number of communication errors
NOTE
The communication error count is temporarily stored in the RAM memory. The value is not stored
in EEPROM, and so is cleared to 0 when power is reset and the inverter is reset.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......