(A) Application parameters
Parameters
5 - 578
●
If offline auto tuning has ended in error (see the table below), motor constants are not set.
Perform an inverter reset and restart tuning.
●
When tuning is ended forcibly by pressing STOP/RESET key or turning OFF the start signal (STF or
STR) during tuning, offline auto tuning does not end properly. (The motor constants have not
been set.)
●
Perform an inverter reset and restart tuning.
●
If using a motor falling under the following conditions, set the value of Pr. 9 "Electronic thermal
O/L relay" as shown below after tuning is complete.
–
If the rated power supply of the motor is 200/220 V(400/440 V) 60 Hz, set the rated motor
current multiplied by 1.1 in Pr. 9.
–
For a motor with a PTC thermistor, thermal protector or other thermal detection, set "0" (motor
overheat protection by inverter invalid) in Pr. 9 to protect the motor from overheating.
Error display
Error cause
Countermeasures
8
Forced end
Set "11" to Pr. 96 and retry.
9
Inverter protective function operation
Make the setting again.
91
The current limit (stall prevention) function is
activated.
Set the acceleration/deceleration time longer.
Set Pr. 156 "Stall prevention operation selection"
= "1".
92
The converter output voltage fell to 75% of
the rated value.
Check for the power supply voltage fluctuation.
93
Calculation error
The motor is not connected.
Check the motor wiring and make the setting
again.
94
Rotation tuning frequency setting error
(The frequency command for the tuning was
given to exceed the maximum frequency
setting, or to be in the frequency jump
range.)
Check the Pr. 1 "Maximum frequency "and Pr. 31
to Pr. 36 Frequency jump settings.
Tab. 5-249:
Error display
NOTES
An instantaneous power failure occurring during tuning will result in a tuning error.
After power is restored, the inverter goes into the normal operation. Therefore, when STF (STR)
signal is ON, the motor runs in the forward (reverse) rotation.
Any alarm occurring during tuning is handled as in the normal operation. Note that even if a retry
operation has been set, retry is not performed.
The set frequency monitor displayed during the offline auto tuning is 0 Hz.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......