background image

www.go4b.com

P300 Series

INDUCTIVE PROXIMITY SENSOR

INSTALLATION INSTRUCTIONS

OPERATION MANUAL

Part No’s. P3003V10AI, P3004V10AI, P3003V34AI

Summary of Contents for P300 Series

Page 1: ...www go4b com P300 Series INDUCTIVE PROXIMITY SENSOR INSTALLATION INSTRUCTIONS OPERATION MANUAL Part No s P3003V10AI P3004V10AI P3003V34AI...

Page 2: ...THIS PAGE IS INTENTIAONALLY LEFT BLANK...

Page 3: ...ENSIONS Page 8 INSTALLATION Page 8 9 STANDARD WIRING DIAGRAM Page 10 11 TESTING COMMISSIONING Page 12 TROUBLESHOOTING GUIDE Page 13 PRODUCT WARRANTY Page 14 TABLE OF CONTENTS Rotating parts can crush...

Page 4: ...esponsibility of the user unless you have asked 4B to perform these tasks B All installation and wiring must be in accordance with Local and National Electrical Codes and other standards applicable to...

Page 5: ...ction work at the facility hours of operation animal or insect infestation and the real world experience of knowing how your employees perform their jobs The personnel or person you select to install...

Page 6: ...SPECIFICATIONS WARNING Rotating machinery can cause serious injury or death Always lockout and tagout the machine prior to installation PAGE 6 Supply Voltage P3003V10AI and P3004V10AI 24 240 VAC VDC P...

Page 7: ...APPROVALS ATEX Baseefa12ATEX0226X 1G Ex ma IIC T4 Ga 1D Ex ma IIIC T200 110 C Da Tamb 15 C to 50 C IP66 IECEx IECEx BAS 12 0118X Ex ma IIC T4 Ga Ex ma IIIC T200 110 C Da Tamb 15 C to 50 C IP66 PAGE 7...

Page 8: ...nvironments the cabling should be segregated from any high current carrying and ideally shielded cables should be used for long distance runs Red LED output indicates target sensed IMPORTANT The sensi...

Page 9: ...rd Therefore this device and its target must be equipped with a guard Shaft 20 mm Diameter Ferrous Target 6mm Min Ferrous Target 8 mm 5 16 in Max Non Ferrous Target 5 mm 3 16 in Max PAGE 9 P300 Shown...

Page 10: ...rigid metal conduit to protect the cables from the sensors to the control unit Conduit systems can channel water due to ingress and condensation directly to sensors and sensor connections which over t...

Page 11: ...PAGE 11 P3003V34AI V to Blue P3003V34AI V to Brown Note NPN Energised top left is the standard wiring to use this sensor with all the 4B controllers...

Page 12: ...mity switch be sure that the target is not within range of the sensor prior to testing Use a metal putty knife or a small piece of metal and place it between the sensing face of the P300 and the targe...

Page 13: ...k 30mm minimum Check that the machinery is rotating and that the target is actually leaving the sensor before reappearing Check that background metalwork behind target is far enough away so as not to...

Page 14: ...e abuse or misapplications as authorized by law 4B specifically disclaims all warranties that the product is fit or merchantable for a particular purpose 3 NO WARRANTY BY SAMPLE OR EXAMPLE Although 4B...

Page 15: ...PAGE 15 THIS PAGE IS INTENTIAONALLY LEFT BLANK...

Page 16: ...ca Tel 27 0 11 708 6114 Fax 27 0 11 708 1654 4B AUSTRALIA Building 1 41 Bellrick Street Acacia Ridge Queensland 4110 Australia Tel 61 0 7 3216 9365 Fax 61 0 7 3219 5837 4B COMPONENTS LTD 625 Erie Aven...

Reviews: