background image

GENERAL

These condensing units are designed for outdoor installation
on a roof or at ground level. Every unit is completely piped and
wired at the factory and is shipped ready for immediate instal-
lation. Only the liquid and suction lines to the evaporator coil,
the filter drier, the control wiring and the main power wiring are
required to complete the installation. Each unit is dehydrated,
evacuated, leak tested and pressure tested at 450 psig before
being pressurized with a holding charge of refrigerant-22 for
shipment and/or storage.

All controls are located in the front of the unit and are readily
accessible for maintenance, adjustment and service. All wiring
(power and control) can be made through the front of the unit.

REFERENCE

This instruction covers the installation and operation of the
basic condensing unit. For information on the installation and
operation of the evaporator blower units, refer to instruction
Form 550.23-N4Y.

All accessories come with a separate Installation Manual.

Refer to Parts Manual for complete listing of replacement parts
on this equipment.

All forms may be ordered from:

Publications Distribution Center
Unitary Products Group
P.O. Box 1592, York, Pa.  17405

INSPECTION

As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier’s freight bill. A separate
request for inspection by the carrier’s agent should be made in
writing. 

SPLIT-SYSTEM

CONDENSING UNITS

(AIR COOLED)

INSTALLATION INSTRUCTION

Supersedes:  550.23-N6Y (398)

550.23-N6Y   (998)

Installer should pay particular attention to the words:  

NOTE, CAUTION and WARNING. Notes are intended to clarify or make

the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury
and/or equipment damage may result if installation procedure is not handled properly.

MODELS H3CE180 & 240 

035-15470

® 

O

O

O

Summary of Contents for H3CE180

Page 1: ...f the evaporator blower units refer to instruction Form 550 23 N4Y All accessories come with a separate Installation Manual Refer to Parts Manual for complete listing of replacement parts on this equi...

Page 2: ...Secure Owner s Approval 12 Maintenance 12 Cleaning Condenser Surface 13 Lubrication 12 Compressor Replacement 12 TABLES No Description Page 1 Unit Application Data 3 2 Physical Data 4 3 Electrical Dat...

Page 3: ...4 Footers under the slab that extend below the frost line are recom mended Anystrainontherefrigerantlinesmaycausearefrigerant leak Theslabshouldnotbetiedtothebuildingfoundationbecause noise and vibra...

Page 4: ...r general installation procedure Refer to Figure 3 for typical field wiring COMPRESSOR CRANKCASE HEATER The compressor is equipped with a crankcase heater to prevent refrigerant from mixing with crank...

Page 5: ...R S H 3 C E 1 8 0 K 1 E U 1 8 0 H 3 C E 2 4 0 L 3 E U 2 4 0 3 P H A S E L I N E V O L T A G E P O W E R S U P P L Y 3 P H A S E L I N E V O L T A G E P O W E R S U P P L Y 3 P H A S E L I N E V O L T...

Page 6: ...A C C E S S E X T E R N A L P R E S S U R E G A U G E F I T T I N G S C O N T R O L B O X A C C E S S 9 1 3 2 7 6 7 8 7 1 3 2 3 9 7 8 1 3 1 4 3 0 3 4 2 4 1 2 1 2 1 8 C D F E F E F A B All dimensions a...

Page 7: ...on line must be sized for both pressure drop and for oil return For certain piping arrangements different suction line sizes may have to be used The velocity of the suction gas must always be great en...

Page 8: ...oor system performance but could also damage the expansion valve TABLE 5 LIQUID LINES Liquid Line2 Inches O D 5 8 0 113 lb ft 7 8 0 237 lb ft Suction Line2 Inches O D 1 5 8 0 018 lb ft 2 1 8 0 031 lb...

Page 9: ...rom the access port on the liquid line service valve of the condensing unit to the hole through the suction disc on the evaporator coil 3 Unbraze the coil s liquid line disc while maintaining a flow o...

Page 10: ...f the refrigerant for the total system by adding the required charge for the outdoor unit the indoor unit and the refrigerant lines using information in Tables 2 Physical Data and 6 Refrigerant Line C...

Page 11: ...F Ambient 95 F Ambient 85 F Ambient 75 F Ambient Charging Curve H CE240 200 250 300 350 400 57 62 67 72 77 82 87 92 97 Suction Pressure Discharge Pressure 115 F Ambient 105 F Ambient 95 F Ambient 85...

Page 12: ...rgized locking out cooling operation until the call for cooling has been removed When Y1 is returned to 0 volts the LOR coil is no longer energized closing the LOR 1 contacts and removing the lock out...

Page 13: ...ration to 0 F SAFETY FEATURES 1 The compressor is protected against over current and excessive temperature as described in the Sequence of Operation 2 The compressor is equipped with a crankcase heate...

Reviews: