background image

LIMITATIONS

These units must be installed in accordance with all national
and local safety codes. If no local codes apply, installation must
conform with the appropriate national codes. See Table 1 for
Unit Application Data. Units are designed to meet National
Safety Code Standards. If components are to be added to a
unit to meet local codes, they are to be installed at the dealer’s
and/or the customer’s expense.

LOCATION

Use the following guidelines to select a suitable location for
these units.

1. The condensing unit is designed for outdoor installation

only. The condenser fans are the propeller type and are not
suitable for use with duct work.

2. The condensing unit and the evaporator blower should be

installed as close together as possible and with a minimum
number of bends in the refrigerant piping. Refer to
“REFRIGERANT PIPING” for additional information.

3. The condensing unit should not be installed where normal

operating sounds may be objectionable. On either rooftop
or ground level installations, rubber padding can be applied
between the base rails and their supports to lessen any
transmission of vibration.

ROOF-TOP LOCATIONS

Be careful not to damage the roof. Consult the building contrac-
tor or architect if the roof is bonded. Choose a location with
adequate structural strength to support the unit.

The condensing unit must be mounted on solid level supports.
The supports can be channel iron beams or wooden beams
treated to reduce deterioration.

A minimum of two (2) beams are required to support each unit.
The beams should: (1) Be positioned perpendicular to the roof
joists. (2) Extend beyond the dimensions of the unit to distribute
the load on the roof. (3) Be capable of adequately supporting
the entire unit weight. Refer to Figure 1 and Table 2 for load
distribution and weights.

These beams can usually be set directly on the roof. Flashing
is not required.

NOTE: On bonded roofs, check for special installation require-

ments.

GROUND LEVEL LOCATIONS

The units must be installed on a one-piece level concrete slab
with a minimum thickness of 4 inches. The length and width
should be at least 6 inches greater than the units overall base
dimensions. Refer to Figure 4.

Footers under the slab that extend below the frost line are recom-
mended. Any strain on the refrigerant lines may cause a refrigerant
leak. The slab should not be tied to the building foundation because
noise and vibration will telegraph into the building.

A unit can also be supported by concrete piers. These piers
should (1) extend below the frost line, (2) be located under the
unit’s four corners, and (3) be sized to carry the entire unit
weight. Refer to Figure 1 and Table 2 for the center of gravity
and unit weight.

CAUTION: Care should be taken to protect the unit from

tampering and unauthorized persons from injury.
Screws on access panels will prevent casual tam-
pering. Additional safety precautions such as
fences around the unit or locking devices on the
panels may be advisable. Check local authorities
for safety regulations.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any pack-
aging until the unit is near the place of installation.

Rig the unit by attaching chain or cable slings with hooks to the
round lifting holes provided in the base rails. 

CAUTION: Spreaders, longer than the largest dimension

across the unit, MUST be used across the top of
the unit.

WARNING: BEFORE LIFTING A UNIT, MAKE SURE THAT ITS

WEIGHT IS DISTRIBUTED EQUALLY ON THE
CABLES SO THAT IT WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift from the front,
rear or the compressor end only through the slotted openings
provided in the base rails.

CAUTION: LENGTH OF FORKS MUST BE A MINIMUM OF

54" (when lifting from the compressor end of the
unit) and a MINIMUM OF 42" (when lifting from the
front or rear of the unit).

Remove the nesting brackets from the four corners on top of
the unit. All screws that are removed to take these brackets off
must be replaced on the unit.

INSTALLATION

MODEL

180 & 240 MBH

Voltage Variation

1

Min. / Max.

208/230-3-60

187 / 252

460-3-60

432 / 504

575-3-60

540 / 630

Ambient Air on 
Condenser Coil

Min. / Max.

Standard

35

°

F / 115

°

F

with Head Pressure

Control

0

°

F / 115

°

F

1. Utilization Range "A" in ARI Standard 110.

2. The minimum allowed ambient temperature for mechanical cooling without the head pres-
  sure control accessory installed must be raised if the indoor air flow is less than the mini-
  mum value given in the capacity tables.

TABLE 1 - UNIT APPLICATION DATA

FIG. 1 - CENTER OF GRAVITY

Unit

Dim. (in.)

A

B

180 Mbh

16

32

240Mbh

16

32

550.23-N6Y

Unitary Products Group

3

Summary of Contents for H3CE180

Page 1: ...f the evaporator blower units refer to instruction Form 550 23 N4Y All accessories come with a separate Installation Manual Refer to Parts Manual for complete listing of replacement parts on this equi...

Page 2: ...Secure Owner s Approval 12 Maintenance 12 Cleaning Condenser Surface 13 Lubrication 12 Compressor Replacement 12 TABLES No Description Page 1 Unit Application Data 3 2 Physical Data 4 3 Electrical Dat...

Page 3: ...4 Footers under the slab that extend below the frost line are recom mended Anystrainontherefrigerantlinesmaycausearefrigerant leak Theslabshouldnotbetiedtothebuildingfoundationbecause noise and vibra...

Page 4: ...r general installation procedure Refer to Figure 3 for typical field wiring COMPRESSOR CRANKCASE HEATER The compressor is equipped with a crankcase heater to prevent refrigerant from mixing with crank...

Page 5: ...R S H 3 C E 1 8 0 K 1 E U 1 8 0 H 3 C E 2 4 0 L 3 E U 2 4 0 3 P H A S E L I N E V O L T A G E P O W E R S U P P L Y 3 P H A S E L I N E V O L T A G E P O W E R S U P P L Y 3 P H A S E L I N E V O L T...

Page 6: ...A C C E S S E X T E R N A L P R E S S U R E G A U G E F I T T I N G S C O N T R O L B O X A C C E S S 9 1 3 2 7 6 7 8 7 1 3 2 3 9 7 8 1 3 1 4 3 0 3 4 2 4 1 2 1 2 1 8 C D F E F E F A B All dimensions a...

Page 7: ...on line must be sized for both pressure drop and for oil return For certain piping arrangements different suction line sizes may have to be used The velocity of the suction gas must always be great en...

Page 8: ...oor system performance but could also damage the expansion valve TABLE 5 LIQUID LINES Liquid Line2 Inches O D 5 8 0 113 lb ft 7 8 0 237 lb ft Suction Line2 Inches O D 1 5 8 0 018 lb ft 2 1 8 0 031 lb...

Page 9: ...rom the access port on the liquid line service valve of the condensing unit to the hole through the suction disc on the evaporator coil 3 Unbraze the coil s liquid line disc while maintaining a flow o...

Page 10: ...f the refrigerant for the total system by adding the required charge for the outdoor unit the indoor unit and the refrigerant lines using information in Tables 2 Physical Data and 6 Refrigerant Line C...

Page 11: ...F Ambient 95 F Ambient 85 F Ambient 75 F Ambient Charging Curve H CE240 200 250 300 350 400 57 62 67 72 77 82 87 92 97 Suction Pressure Discharge Pressure 115 F Ambient 105 F Ambient 95 F Ambient 85...

Page 12: ...rgized locking out cooling operation until the call for cooling has been removed When Y1 is returned to 0 volts the LOR coil is no longer energized closing the LOR 1 contacts and removing the lock out...

Page 13: ...ration to 0 F SAFETY FEATURES 1 The compressor is protected against over current and excessive temperature as described in the Sequence of Operation 2 The compressor is equipped with a crankcase heate...

Reviews: