background image

REFRIGERANT PIPING

GENERAL GUIDELINES

Many service problems can be avoided by taking adequate pre-
cautions to provide an internally clean and dry system and by using
procedures and materials that conform with established standards.

Use hard drawn copper tubing where no appreciable amount
of bending around pipes or other obstructions is necessary.
Use long radius ells wherever possible with one exception—
short radius ells for the traps in all suction risers. If soft copper
is used, care should be taken to avoid sharp bends which may
cause a restriction.

Pack fiber glass insulation and a sealing material such as
permagum around refrigerant lines where they penetrate a wall
to reduce vibrations and to retain some flexibility.

Support all refrigerant lines at minimum intervals with suitable
hangers, brackets or clamps.

Braze all copper to copper joints with Silfos-5 or equivalent
brazing material. Do not use soft solder.

Insulate all suction lines with a minimum of 1/2" ARMAFLEX or
equal. Liquid lines exposed to direct sunlight and/or high tem-
peratures must also be insulated.

Never solder suction and liquid lines together. They can be taped
together for convenience and support purposes, but they must be
completely insulated from each other.

A filter-drier MUST be installed in the liquid line of every system
to prevent dirt and moisture from damaging the system. A prop-
erly-sized filter-drier is shipped with each condensing unit for field
installation near the evaporator coil. The filter-drier is shipped
inside the unit control box.

NOTE: Installing a filter-drier does not eliminate the need for

the proper evacuation of a system before it is charged.

A moisture indicating sight-glass may be field installed in liquid
line(s) between the filter-drier and the evaporator coil.  The
moisture indicating sight-glass can be used to check for excess
moisture in the system or used as visual means to verify
refrigerant charge.

LINE SIZING

When sizing refrigerant lines for a split-system air conditioner,
check the following:

1. Suction line pressure drop due to friction at full capacity,

2. Liquid line pressure drop due to friction at full capacity,

3. Suction line velocity for oil return at part capacity, and

4. Liquid line pressure drop due to static head.

NOTE: Never base refrigerant line sizes on the OD of the

suction and liquid connections on the unit.

Tables 4 and 5 list friction losses for both the suction and liquid
lines on the system. Table 6 shows the amount of refrigerant
charge required per foot of refrigerant line.

When the evaporator coil is below the condensing unit, the
suction line must be sized for both pressure drop and for oil
return. For certain piping arrangements, different suction line
sizes may have to be used. The velocity of the suction gas must
always be great enough to carry oil back to the compressor.

When the condensing unit is below the evaporator coil, the
liquid line must be designed for the pressure drop due to both
friction loss and vertical rise. If the total pressure drop exceeds
40 psi, some refrigerant may flash before it reaches the thermal
expansion valve. This flashing will not only cause erratic valve
operation and poor system performance, but could also dam-
age the expansion valve.

SERVICE VALVES

These condensing units have service valves on the compres-
sor suction line and on the liquid line leaving the condenser coil.

The liquid and suction line service valves are shipped from the
factory front-seated and closed with the valve stem in the
maximum clockwise position. 

The liquid and suction line service valves have a 1/4" male flare
access port for evacuating, charging and pressure checking the
system.

NOTE: Never remove a cap from an access port unless the

valve is fully back-seated with its valve stem in the
maximum counter-clockwise position because the re-
frigerant charge will be lost. ALWAYS USE A REFRIG-
ERATION VALVE WRENCH TO OPEN AND CLOSE
THESE SERVICE VALVES.

Model

Designation

Nominal

Capacity

(Tons)

Refrigerant
Flow Rate

3

(Lbs./Min.)

Type L

Copper Tubing

(Inches O.D.)

Refrigerant

Gas

Velocity

(FT./Min.)

Friction

Loss

4,5

(PSI/100 Ft.)

180 Mbh

Full

Capacity

15

45

1-5/8
2-1/8

2300
1360

2.5
0.6

Part

Capacity

8-1/2

25.5

1-5/8
2-1/8

1150

   770

6

0.7
0.2

240 Mbh

Full

Capacity

20

60

1-5/8
2-1/8
2-5/8

3120
1800
1200

4.3
1.2
0.4

Part

Capacity

10

30

1-5/8
2-1/8
2-5/8

1560

   900

6

   600

6

1.2
0.3
0.1

1All horizontal suction lines should be pitched at least 1 inch every 20 feet in the direction of the refrigerant flow to aid the return of oil to the compressor.

2

Every vertical suction riser greater than 25 feet in height should have a “P” trap at the bottom to facilitate the return of oil to the compressor. Use short radius fittings for these traps.

3

Based on Refrigerant-22 at the nominal capacity of the condensing unit, a suction temperature of 40

°

F and a liquid temperature of 105

°

F.

4

Although suction lines should be sized for a friction loss equivalent to a 2

°

F change in saturation temperature (or approximately 3 psi), sizing the lines for the proper return of oil

  is more important.

5

These friction losses do not include any allowances for valves or fittings.

6

Since the refrigerant gas velocity may be too low to maintain good oil return up a vertical riser, use the next smaller size. The larger size may be used for horizontal runs for a smaller

  pressure drop.

TABLE 4 - SUCTION LINES

1,2

550.23-N6Y

Unitary Products Group

7

Summary of Contents for H3CE180

Page 1: ...f the evaporator blower units refer to instruction Form 550 23 N4Y All accessories come with a separate Installation Manual Refer to Parts Manual for complete listing of replacement parts on this equi...

Page 2: ...Secure Owner s Approval 12 Maintenance 12 Cleaning Condenser Surface 13 Lubrication 12 Compressor Replacement 12 TABLES No Description Page 1 Unit Application Data 3 2 Physical Data 4 3 Electrical Dat...

Page 3: ...4 Footers under the slab that extend below the frost line are recom mended Anystrainontherefrigerantlinesmaycausearefrigerant leak Theslabshouldnotbetiedtothebuildingfoundationbecause noise and vibra...

Page 4: ...r general installation procedure Refer to Figure 3 for typical field wiring COMPRESSOR CRANKCASE HEATER The compressor is equipped with a crankcase heater to prevent refrigerant from mixing with crank...

Page 5: ...R S H 3 C E 1 8 0 K 1 E U 1 8 0 H 3 C E 2 4 0 L 3 E U 2 4 0 3 P H A S E L I N E V O L T A G E P O W E R S U P P L Y 3 P H A S E L I N E V O L T A G E P O W E R S U P P L Y 3 P H A S E L I N E V O L T...

Page 6: ...A C C E S S E X T E R N A L P R E S S U R E G A U G E F I T T I N G S C O N T R O L B O X A C C E S S 9 1 3 2 7 6 7 8 7 1 3 2 3 9 7 8 1 3 1 4 3 0 3 4 2 4 1 2 1 2 1 8 C D F E F E F A B All dimensions a...

Page 7: ...on line must be sized for both pressure drop and for oil return For certain piping arrangements different suction line sizes may have to be used The velocity of the suction gas must always be great en...

Page 8: ...oor system performance but could also damage the expansion valve TABLE 5 LIQUID LINES Liquid Line2 Inches O D 5 8 0 113 lb ft 7 8 0 237 lb ft Suction Line2 Inches O D 1 5 8 0 018 lb ft 2 1 8 0 031 lb...

Page 9: ...rom the access port on the liquid line service valve of the condensing unit to the hole through the suction disc on the evaporator coil 3 Unbraze the coil s liquid line disc while maintaining a flow o...

Page 10: ...f the refrigerant for the total system by adding the required charge for the outdoor unit the indoor unit and the refrigerant lines using information in Tables 2 Physical Data and 6 Refrigerant Line C...

Page 11: ...F Ambient 95 F Ambient 85 F Ambient 75 F Ambient Charging Curve H CE240 200 250 300 350 400 57 62 67 72 77 82 87 92 97 Suction Pressure Discharge Pressure 115 F Ambient 105 F Ambient 95 F Ambient 85...

Page 12: ...rgized locking out cooling operation until the call for cooling has been removed When Y1 is returned to 0 volts the LOR coil is no longer energized closing the LOR 1 contacts and removing the lock out...

Page 13: ...ration to 0 F SAFETY FEATURES 1 The compressor is protected against over current and excessive temperature as described in the Sequence of Operation 2 The compressor is equipped with a crankcase heate...

Reviews: