555-233-119
946
Issue 5 October 2002
Notes:
a. This error indicates the DATA-BD portion of the Processor circuit pack
stopped functioning. Since the Processor circuit pack cannot be reset via
the reset board PCSS command, the Data Channel Reset Test (#107) in
the Long Test Sequence for the DATA-CHLs must be used to reset it as
follows:
1. Issue the list data command to determine if one, or more, Data
Channels (DATA-CHLs) is administered.
NOTE:
A Data Channel (DATA-CHL) is identified by a “type” value of
“netcon.”
2. If a Data Channel (DATA-CHL) is not administered, use the add
data-module [<ext> | next] command to administer a DATA-CHL.
3. From the form resulting from the list data command, choose a Data
Channel (DATA-CHL).
4. Issue the test data-module <ext> long command using the
extension for the DATA-CHL chosen in Step 3.
!
WARNING:
Issuing this command drops all data channel extensions. See
DATA-CHL (Data Channel) Maintenance documentation first.
If the red LED stays on, then replace the Processor circuit pack.
769 (e)
4358
None
1025 (f)
4363
NPE Audit Test (#50)
test network-control [a | b]
sh
1538 (g)
Data Channel Reset
Test (#107)
MINOR
ON
test data-module <ext> l
3840 (h)
Any
None
3999(i)
Any
None
1.
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
Table 168.
Data Channel Processor Circuit Pack Error Log Entries — Continued
Error Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
Continued on next page