Maintenance Objects
555-233-119
784
Issue 5 October 2002
Table 105.
ATM Board DSP Test (#1293)
Error
Code
Test
Result
Description/Recommendation
1002
ABORT
Could not allocate time slots. Traffic could be heavy or time slots could be
out-of-service
Run display errors, and follow associated repair procedures for TDM-BUS.
Retry the command up to 3 times at 1-minute intervals.
1003
ABORT
Could not allocate a tone detector. Too few tone detectors present or tone
detectors out-of-service.
Run display errors, and follow the repair procedures associated with any
TTR-LEV (TTR Level) errors that appear.
Make sure that there is at least one tone detector on the network that holds
the ATM-TRK circuit pack.
Resolve any TONE-PT (Tone Generator) errors listed in the Error Log.
Retry the command up to 3 times at 1-minute intervals.
1962
ABORT
All DSPs are busy. This is a very unlikely event.
Retry the command up to 3 times at 1-minute intervals.
2000
ABORT
Test timed out.
If the ATM-TRK circuit pack is in standby, reset the board and run the test
again after the ATM-TRK circuit pack is inserted.
Examine the Error Log for Error 1218 (bad DSP).
Run the test again.
2100
ABORT
Could not allocate required system resources.
2302
ABORT
Inconsistent uplink message from the ATM-TRK circuit pack.
2500
ABORT
Internal system error
Retry the command up to 5 times at 1-minute intervals.
2752
ABORT
Circuit pack not a TN2305A/2306A.
Continued on next page