BRI-BD/LGATE-BD (ISDN-BRI Line Circuit Pack)
Issue 5 October 2002
795
555-233-119
Table 108.
TEST #595 LANBIC Receive Parity Error Counter Test
Error
Code
Test
Result
Description/ Recommendation
2000
ABORT
Response to the test was not received from the circuit pack within the
allowable time period.
1. If the test aborts repeatedly a maximum of 5 times, reset the circuit
pack with busyout board PCSS and reset board PCSS.
2. If the test aborts again, replace the circuit pack.
2100
ABORT
Could not allocate the necessary system resources to run this test.
2012
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1-10
FAIL
The circuit pack is still detecting errors of this type. The error code indicates
the value of the on-board error counter.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If the test continues to fail, verify the validity of the Packet Bus. Run the
Packet Bus maintenance test with test pkt P long.
3. If the Packet Bus test passes, check the validity of the circuit pack.
Execute a test that involves data transmission onto the Packet Bus. For
example, the BRI may use the connectivity tests of the port-level
maintenance object (BRI-PORT) by executing test port PCSSpp.
Refer to the repair procedures for the executed test if it fails.
Otherwise, go to the next step.
4. Other circuit packs on the Packet Bus may be the cause of the parity
error. Use display errors to check the Error Log for other circuit packs
that are alarmed. If any alarms are present for the other circuit packs,
retire those alarms also. Rerun the LANBIC Receive Parity Error
Counter Test (#595) on this circuit pack.
PASS
No errors detected by circuit pack.
Continued on next page