
555-233-119
1082
Issue 5 October 2002
SAKI Sanity Test (#53)
This test is destructive. This test resets the circuit pack.
0
NO BOARD
The test could not relate the internal ID to the port (no board).
This could be due to incorrect translations, no board is inserted, an
incorrect board is inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the add
ds1 UUCSS command to administer the DS1 interface if it is not
already administered.
2. If board was already administered correctly, check the error log to
determine if the board is hyperactive. If this is the case, the board is
shut down. Reseating the board will re-initialize the board.
3. If the board was found to be correctly inserted in step 1, issue the
busyout board command.
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
This should re-establish the linkage between the internal ID and the port.
Table 225.
TEST #53 SAKI Sanity Test
Error
Code
Test Result
Description/ Recommendation
None
ABORT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1005
ABORT
Wrong circuit pack configuration to run this test. This error applies only to
DS1 Interface circuit packs. It means the DS1 Interface circuit pack is
providing timing for the system and, therefore, it cannot be reset without
major system disruptions.
1. If the circuit pack needs to be reset, then set synchronization to
another DS1 Interface circuit pack or to the Tone-Clock circuit pack
and try again. Refer to "SYNC (Synchronization)".
Continued on next page
Table 224.
TEST #52 Control Channel Looparound Test — Continued
Error
Code
Test Result
Description/ Recommendation
Continued on next page