Air Conditioning System: 7B-14
Normal:
0.23 – 0.36
(2.3 – 3.6)
(33 – 51)
n
p
Abnormal:
Negative pressure
Normal:
1.24 – 1.52
(12.4 – 15.2)
(176 – 216)
n
p
Abnormal:
0.7 – 1.0
(7 – 10)
(100 – 142)
During A/C operation, the
low pressure side
sometimes indicates
negative pressure, and
sometimes normal
pressure. Also high
pressure side reading
fluctuates between the
abnormal and normal
pressure.
Expansion valve is
frozen due to moisture
in the system, and
temporarily shuts off
the refrigeration cycle.
Replace expansion
valve.
Replace desiccant.
Evacuate A/C system
and recharge with
fresh refrigerant.
0.05 – 0.15
(0.5 – 1.5)
(4.2 – 21.3)
0.7 – 1.0
(7 – 10)
(100 – 142)
Both low and high
pressure sides indicate
low readings.
Output air is slightly cold.
Insufficient refrigerant
in system
(Refrigerant leaking).
Using leak detector,
check for leaks and
repair as necessary.
Recharge refrigerant to
a specified amount.
If the pressure reading
is almost 0 when the
manifold gauges are
attached, check for any
leaks, repair them, and
evacuate the system.
0.4 – 0.6
(4 – 6)
(56.9 – 85.3)
Pressure on low pressure
side is high.
Pressure on high pressure
side is low.
Both pressure becoming
equal right after A/C is
turned OFF.
Internal leak in
compressor.
Inspect compressor
and repair or replace
as necessary.
0.35 – 0.45
(3.5 – 4.5)
(50 – 64)
2.0 – 2.5
(20 – 25)
(285 – 355)
High pressure reading on
both low and high pressure
sides.
Overcharged A/C
system.
Adjust refrigerant to
specified amount.
Faulty condenser
cooling operation.
Clean condenser.
Faulty radiator cooling
fan operation.
Inspect and repair
radiator cooling fan.
High pressure reading on
both low and high pressure
sides.
Low pressure side tubing
is not cold when touched.
Presence of air in A/C
system
(Improperly
evacuated).
Replace desiccant.
Inspect quantity of
compressor oil and
presence of
contaminants in oil.
Evacuate system and
recharge with fresh
refrigerant.
0.45 – 0.55
(4.5 – 5.5)
(64 – 78)
High pressure reading on
both low and high pressure
sides.
Large amount of frost or
dew on the low pressure
side tubing.
Faulty expansion
valve.
Refrigerant flow is not
regulated properly.
Replace expansion
valve.
Condition
Possible cause
Correction
Manifold gauge
MPa (kg/cm
2
) (psi)
Detail
Lo
Hi
Содержание SWIFT RS415 2017
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 316: ...1D 53 Engine Mechanical Main Bearings Crankshaft and Cylinder Block Components S4RS0A1406035 I4RS0A140016...
Страница 331: ...Engine Lubrication System 1E 2 I3RH0B150001...
Страница 404: ...1K 6 Exhaust System...
Страница 452: ...2D 8 Wheels and Tires...
Страница 464: ...3A 11 Drive Shaft Axle...
Страница 650: ...5A 110 Automatic Transmission Automatic Transaxle Assembly Components S4RS0A5106025 I3RM0B510053...
Страница 722: ...5B 13 Manual Transmission Manual Transaxle Assembly Components S4RS0A5206028 I4RS0A520013...
Страница 760: ...5C 14 Clutch...
Страница 762: ...6 ii Table of Contents Special Tool 6C 38...
Страница 812: ...6C 39 Power Assisted Steering System...
Страница 860: ...7B 35 Air Conditioning System...
Страница 1069: ...Wiring Systems 9A 62 GEAR ABS BELT DOOR CHARGE IMMOBI BRAKE FUEL RADIO 15A 40 32 5 WHT RED J B G33 G28 1 2 I4RS0A910943...
Страница 1192: ...9L 5 Paint Coatings I4RS0A9C0004 A Apply sealant...
Страница 1198: ...9M 2 Exterior Trim Splash Guard If Equipped Components S4RS0A9D06006 A A A A 1 I4RS0A980010 1 Side sill splash guard...
Страница 1255: ...Prepared by 1st Ed Dec 2004...
Страница 1256: ...21 mm 99500 63J00 24E 99500 63J00 24E SERVICE MANUAL VOLUME 1 OF 2 SERVICE MANUAL VOL 1 OF 2...
Страница 1257: ...29 mm 99500 63J00 24E 99500 63J00 24E SERVICE MANUAL VOLUME 2 OF 2 SERVICE MANUAL VOL 2 OF 2...