Functions
6-202
7SA6 Manual
C53000-G1176-C156-2
2711
>AR Start
general fault detection for the internal automatic
reclosure function (only required for action time),
2715
>Trip 1pole AR
trip command 1-pole for the internal automatic reclosure
function,
2716
>Trip 3pole AR
trip command 3-pole for the internal automatic reclosure
function,
If only three-pole reclose cycles are to be executed, it is sufficient to assign the binary
input “
>Trip 3pole AR
” (F.No
2716
) for the trip signal. Figure 6-109 shows an
example. The overreaching stages of the external protection are again enabled by
“
AR 1.CycZoneRel
” (F.No
2889
) and if applicable by further cycles.
Figure 6-108 Connection example with external protection device for 1-/3-pole reclosure;
AR control mode =
with TRIP
Figure 6-109 Connection example with external protection device for 3-pole reclosure;
AR control mode =
with TRIP
7SA6
AR Start
Tripping L1
Tripping L2
Tripping L3
L+
external
protection device
Relay Pickup
3-phase coupling
L–
L–
L–
only 1-pole
(if nec. for other AR)
>AR Start
>Trip L1 AR
>Trip L2 AR
>Trip L3 AR
AR 1.CycZoneRel
AR 1p Trip Perm
AR Program1pole
7SA6
trip
Tripping
L+
external
protection device
Relay Pickup
L–
L–
L+
(if nec. for other AR)
>AR Start
AR 1p Trip Perm
AR 1.CycZoneRel
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...