Functions
6-174
7SA6 Manual
C53000-G1176-C156-2
Stub Protection
When using the I STUB protection the pick-up thresholds
Iph> STUB
(address
2630
)
and
3I0> STUB
(address
2632
) are usually not critical, as this protection function is
only activated when the line isolator is open which implies that every measured current
should represents a fault current. With a 1
1
/
2
–circuit breaker arrangement similar to
Figure 6-93 it is possible that large short circuit currents flow from busbar A to busbar
B or to feeder 2 via the current transformers. These currents could cause different
transformation errors in the two current transformer sets
I
A
and
I
B
, especially in the
saturation range. The protection should therefore not be set unnecessarily sensitive.
If the minimum short circuit currents on the busbars are known, the pick-up threshold
Iph> STUB
is set somewhat (approx. 10 %) below the minimum two phase short cir-
cuit current,
3I0> STUB
is set below the minimum single-phase current.
The time settings
T Iph STUB
(address
2631
) and
T 3I0 STUB
(address
2633
) are
set to zero for this application, to ensure that the protection has fast operation when
the isolator is open.
For different applications similar considerations as for the other stages apply.
If the
I-Stub
-stage is to trip when switching the line on to a fault with or without a
short delay,
SOTF Time DELAY
(address
2680
, see above and refer to Sub-section
“General”), the parameter
I-STUB SOTF
(address
2635
) is set to
YES
. If using the
stub protection, then set to
NO
as the effect of this protection function only depends on
the position of the isolator.
6.11.3 Settings
Note:
The indicated secondary current values for setting ranges and default settings
refer to I
N
= 1 A. For the nominal current 5 A the current values are to be multiplied
by 5.
Addr.
Setting Title
Setting Options
Default Setting
Comments
2601
Operating Mode
ON
Only Active with Loss of VT
sec. circuit
OFF
Only Active with
Loss of VT sec. cir-
cuit
Operating mode
2680
SOTF Time DELAY
0.00..30.00 sec
0.00 sec
Trip time delay after SOTF
2610
Iph>>
0.10..25.00 A;
∞
2.00 A
Iph>> Pickup
2611
T Iph>>
0.00..30.00 sec;
∞
0.30 sec
T Iph>> Time delay
2612
3I0>> PICKUP
0.05..25.00 A;
∞
0.50 A
3I0>> Pickup
2613
T 3I0>>
0.00..30.00 sec;
∞
2.00 sec
T 3I0>> Time delay
2614
I>> Telep/BI
NO
YES
YES
Instantaneous trip via Teleprot./
BI
2615
I>> SOTF
NO
YES
NO
Instantaneous trip after Swit-
chOnToFault
2620
Iph>
0.10..25.00 A;
∞
1.50 A
Iph> Pickup
2621
T Iph>
0.00..30.00 sec;
∞
0.50 sec
T Iph> Time delay
2622
3I0>
0.05..25.00 A;
∞
0.20 A
3I0> Pickup
2623
T 3I0>
0.00..30.00 sec;
∞
2.00 sec
T 3I0> Time delay
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...