Technical Data
10-38
7SA6 Manual
C53000-G1176-C156
10.16 Fault Location
Start
with trip command or drop-off
Setting range reactance (secondary)
0.005
Ω
/km to 6.500
Ω
/km
2
)
(steps 0.001
Ω
/km) or
0.005
Ω
/mile to 10.000
Ω
/mile
2
)
(steps 0.001
Ω
/mile)
Parallel line compensation
can be switched on/off
Set values are the same as for distance
protection (see Section 10.2)
Load current compensation
correction of the X-value
for single-phase earth faults
can be switched on/off
Output of the fault distance
in
Ω
primary and
Ω
secondary,
in km or miles line
1
),
in % of the line length
1
)
Measuring tolerances
2.5 % of line length
with sinusoidal measured quantities
at 30°
≤ ϕ
k
≤
90° and U
k
/U
N
≥
0.1
Further output options
as analog value 0 mA to 22.5 mA;
(dependent on order variant)
as BCD–code 4 bit units + 4 bit tens +
1 bit hu 1 validity bit
output time, settable
0.01 s to 30.00 s;
∞
(steps 0.01 s)
1
) Output of the fault distance in km, miles, and % requires homogeneous lines.
2
) Secondary values based on I
N
= 1 A; for I
N
= 5 A the impedances are to be divided by 5.
10.17 Circuit Breaker Failure Protection (optional)
Circuit Breaker
Monitoring
Current flow monitoring
0.05 A to 20.00 A
1
)
(steps 0.01 A)
Drop-off to pick-up ratio
approx. 0.95
Tolerance
5 % of the set value or 0.01 A
1
)
Monitoring of circuit-breaker
auxiliary contact position
- for three-pole tripping
binary input for circuit breaker
auxiliary contact
- for single-pole tripping
1 binary input for auxiliary contact per pole
or
1 binary input for series connection NO
contact and NC contact
Note: The circuit breaker failure protection can also operate without the indicated circuit breaker auxiliary contacts, but the
function range is then reduced. Auxiliary contacts are necessary for the circuit breaker failure protection for tripping without
or with a very low current flow (e.g. Buchholz protection), stub fault protection, circuit breaker pole discrepancy monitoring.
1
) Secondary values based on I
N
= 1 A; for I
N
= 5 A the currrent values are to be
multiplied by 5.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...