Appendix
B-10
7SA6 Manual
C53000-G1176-C156-2
2103A
Send Prolong.
Teleprotection for
Distance prot.
0.00..30.00 sec
0.05 sec
Time for send signal prolongation
2107A
Delay for alarm
Teleprotection for
Distance prot.
0.00..30.00 sec
10.00 sec
Time Delay for Alarm
2108
Release Delay
Teleprotection for
Distance prot.
0.000..30.000 sec
0.000 sec
Time Delay for release after pickup
2109A
TrBlk Wait Time
Teleprotection for
Distance prot.
0.00..30.00 sec;
∞
0.04 sec
Transient Block.: Duration external flt.
2110A
TrBlk BlockTime
Teleprotection for
Distance prot.
0.00..30.00 sec
0.05 sec
Transient Block.: Blk.T. after ext. flt.
2201
FCT Direct Trip
DTT Direct Trans-
fer Trip
ON
OFF
OFF
Direct Transfer Trip (DTT)
2202
Trip Time DELAY
DTT Direct Trans-
fer Trip
0.00..30.00 sec;
∞
0.01 sec
Trip Time Delay
2401
FCT SOTF-O/C
Instantaneous High-
Speed SOTF Over-
current
ON
OFF
ON
Inst. High Speed SOTF-O/C is
2404
I>>>
Instantaneous High-
Speed SOTF Over-
current
1.00..25.00 A
2.50 A
I>>> Pickup
2501
FCT Weak Infeed
Weak Infeed (Trip
and/or Echo)
OFF
Echo only
Echo and Trip
Echo only
Weak Infeed function is
2502A
Trip/Echo DELAY
Weak Infeed (Trip
and/or Echo)
0.00..30.00 sec
0.04 sec
Trip / Echo Delay after carrier receipt
2503A
Trip EXTENSION
Weak Infeed (Trip
and/or Echo)
0.00..30.00 sec
0.05 sec
Trip Extension / Echo Impulse time
2505
UNDERVOLTAGE
Weak Infeed (Trip
and/or Echo)
2..70 V
25 V
Undervoltage (ph-e)
2601
Operating Mode
Backup overcurrent ON
Only Active with Loss of VT
sec. circuit
OFF
Only Active with Loss of VT
sec. circuit
Operating mode
2610
Iph>>
Backup overcurrent 0.10..25.00 A;
∞
2.00 A
Iph>> Pickup
2611
T Iph>>
Backup overcurrent 0.00..30.00 sec;
∞
0.30 sec
T Iph>> Time delay
2612
3I0>> PICKUP
Backup overcurrent 0.05..25.00 A;
∞
0.50 A
3I0>> Pickup
2613
T 3I0>>
Backup overcurrent 0.00..30.00 sec;
∞
2.00 sec
T 3I0>> Time delay
2614
I>> Telep/BI
Backup overcurrent NO
YES
YES
Instantaneous trip via Teleprot./BI
2615
I>> SOTF
Backup overcurrent NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
2620
Iph>
Backup overcurrent 0.10..25.00 A;
∞
1.50 A
Iph> Pickup
2621
T Iph>
Backup overcurrent 0.00..30.00 sec;
∞
0.50 sec
T Iph> Time delay
2622
3I0>
Backup overcurrent 0.05..25.00 A;
∞
0.20 A
3I0> Pickup
2623
T 3I0>
Backup overcurrent 0.00..30.00 sec;
∞
2.00 sec
T 3I0> Time delay
2624
I> Telep/BI
Backup overcurrent NO
YES
NO
Instantaneous trip via Teleprot./BI
2625
I> SOTF
Backup overcurrent NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
2630
Iph> STUB
Backup overcurrent 0.10..25.00 A;
∞
1.50 A
Iph> STUB Pickup
2631
T Iph STUB
Backup overcurrent 0.00..30.00 sec;
∞
0.30 sec
T Iph STUB Time delay
2632
3I0> STUB
Backup overcurrent 0.05..25.00 A;
∞
0.20 A
3I0> STUB Pickup
2633
T 3I0 STUB
Backup overcurrent 0.00..30.00 sec;
∞
2.00 sec
T 3I0 STUB Time delay
2634
I-STUB Telep/BI
Backup overcurrent NO
YES
NO
Instantaneous trip via Teleprot./BI
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...