Configuration
5-54
7SA6 Manual
C53000-G1176-C156-2
5.6
Serial Interfaces
Note:
The protection data interfaces for protection transmission are described in Section 6.4
in the protection functions.
The device contains one or more serial interfaces: an operator interface integrated into
the front panel, and — depending on the model ordered — a service interface and a
system interface for connection of a central control system. Certain standards are nec-
essary for communication via these interfaces, which contain device identification,
transfer protocol, and transfer speed.
Configuration of these interfaces is performed using the DIGSI
®
4 software program.
Click on
Setting
in the navigation window and double-click in the data window on
Interfaces
. Next, select the specific data in the resulting dialogue box (Figure 5-
51). The dialogue box contains a varying number of tabs (depending on the capabili-
ties of the PC and the relay) with setting options for the interfaces.
Figure 5-51
DIGSI
®
4, Settings of the PC interface — example
Serial port on PC
In the first tab, you enter the communication interface of the PC which is connected to
the 7SA6 relay (
COM1, COM2,
etc.). Manual entry of settings for data format and
baud-rate need not be made if these values were taken from the “
Operator Inter-
face
” tab or the “
Service interface
” tab (if present). In fact, many settings are
read from DIGSI
®
4 directly via the interface, and the corresponding setting fields are
then inaccessible (see Figure 5-51). Alternatively, the option
Independent of de-
vice
may be selected.
Data exchange is monitored by the PC for the reaction times of the device. You may,
within preset limits, configure maximum relay reaction times. The displayed values
RQ 1 and RQ 2 correspond to the preset reaction times in milliseconds. In general,
these values should not be modified. Modification is only necessary if a time-out often
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...