Installation and Commissioning
8-39
7SA6 Manual
C53000-G1176-C156-2
Interface Profibus
Figure 8-22 Location of jumpers for the configuration of terminating resistors at the interface
Profibus
The terminating resistors can also be connected externally (e.g. to the connection
module) as illustrated in Figure 8-23. In this case, the terminating resistors located on
the RS485 or the Profibus interface module must be disconnected.
Figure 8-23 Termination of interface RS485 (external)
Analog Output
Module
The analog output module AN20 is provided with 2 isolated channels with a current
range from 0 to 20 mA (unipolar, maximum 350
Ω
).
The mounting location on the processor circuit board C–CPU–2 is “B” and/or “D”, de-
pendent on the version (see Figure 8-19).
Figure 8-24 Interface module with the analog output AN20
X3
3
1
2
X4
3
1
2
Jum-
pers
Terminating Resistors
connected
disconnected
X3
1–2
2–3 *)
X4
1–2
2–3 *)
C53207-A322-
2 3 4
B100
B101
*)
Default Setting
392
Ω
221
Ω
392
Ω
+5 V
A/A´
B/B´
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...