Control During Operation
7-44
7SA6 Manual
C53000-G1176-C156-2
even if the operator confirms the opposite. Only if no auxiliary contacts are marshalled,
will the device rely on the confirmation by the operator.
If the test cycle should be cancelled, press the
key in response to the above query,
so that the answer “
No
” is marked. This must be confirmed with the
key. Prior to
the confirmation with the
it is possible to toggle between “Yes” and “
No
” with the
and
keys. Alternatively, the test sequence may also be cancelled by pressing
the
key.
Figure 7-44
Circuit breaker trip test cycle from the front of the device
From PC with
DIGSI
®
4
If the
Online
directory in DIGSI
®
4 is opened with a double click, the operation func-
tions of the device appear in the left hand side of the window.
By clicking on
Test
, a list of the available functions appears on the right hand side of
the display (Figure 7-45).
By a double click on the
Circuit breaker test
, a dialogue window is opened in
which the desired test sequence can be marked for selection.
Following a double click, a prompt for the entry of password No. 4 (for test and diag-
nosis) appears.
After entry of the password and confirmation with
Ok
the test sequence is executed.
In the spontaneous event window, the execution of the test is displayed with the cor-
responding control responses and messages.
ENTER
ENTER
ESC
CB Test
01/08
---------------------
>
CB1tst L1
1
>
CB1tst L2
2
etc.
Select the desired test program or press the
relevant numeric key to select the desired test
sequence.
S
Breaker closed?
>
Yes
No
Press the
to confirm with “
Yes
” and
thereby execute the selected breaker test cy-
cle, or change to ”
No
” with the
key to termi-
nate the test when
is pressed.
ENTER
ENTER
ENTER
PW Test+Diagnose?
=-------
Enter password Nr. 4 (for test and diagnostics)
and confirm with
.
ENTER
MAIN MENU
05/05
---------------------
>
Settings
4
>
Test/Diagnose
5
TEST/DIAGNOSE 07/07
---------------------
>
SIEMENS intern
12
>
CB test
21
CB Test
01/08
---------------------
>
CB1tst L1
1
Control Executed
If confirmed that the CB is closed, the CB test
cycle is executed, subsequently a feedback
message stating successful completion of the
test or a corresponding alarm appears.
:
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...