Functions
6-121
7SA6 Manual
C53000-G1176-C156-2
6.7
Earth Fault Protection in Earthed Systems (optional)
General
In earthed systems, where extremely large fault resistance may exist during earth
faults (e.g. overhead lines without earth wire, sandy soil, or high tower footing resist-
ance) the fault detection of the distance protection will often not pick up because the
resulting earth fault impedance could be outside the fault detection characteristic of
the distance protection.
The Distance Protection 7SA6 has protection functions for such high resistance earth
faults. These options are available:
•
three overcurrent stages with definite time tripping characteristic (definite time),
•
one overcurrent time stage with inverse time characteristic (IDMT) or
•
one zero sequence voltage stage with inverse time characteristic
These four stages are independent of each other and are freely combinable. If the in-
verse time stage is not required, it may be employed as a fourth definite time stage.
Each stage may also be set to be non directional or directional — forward or reverse.
A signal transmission may be combined with these four stages. For each stage it may
be determined if it should coordinate with the signal transmission (refer also to Section
6.8). If the protection is applied in the proximity of transformers, an inrush stabilization
can be activated. Furthermore, blocking by external criteria is possible via binary in-
puts (e.g. for reverse interlocking or external automatic reclosure). During energization
of the protected feeder onto a short circuit, any stage — or several stages — may be
switched to undelayed tripping. If a stage is not required it can be deactivated.
6.7.1
Method of Operation
Measured Value
The earth current is the negative sum of the three phase currents, i.o.w.
I
E
= –3·
I
0
=
–(
I
L1
+
I
L2
+
I
L3
). Depending on the version ordered, and the configured application
for the fourth current input
I
4
of the device, the earth current can be measured or cal-
culated.
If the input
I
4
is connected in the starpoint of the set of current transformers or to a
separate earth current transformer, on the protected feeder, the earth current is direct-
ly available as a measured value.
If the device is fitted with the highly sensitive current input for
I
4
, this current
I
4
is used
with the matching factor
I4/Iph CT
(address
221
, refer to Subsection 6.1.1). As the
linear range of this measuring input is severely limited, this current is only evaluated
up to an amplitude of approximately 1.6 A. In the case of larger currents the device
automatically switches over to the evaluation of the zero sequence current derived
from the phase currents. Naturally, all three phase currents from three current trans-
formers connected in a star arrangement must be available and connected. This al-
lows the processing of the earth current both when very small and also larger earth
fault currents may occur.
If the fourth current input
I
4
is otherwise utilized, e.g. for a transformer starpoint current
or for the earth current of a parallel line, the device calculates the earth current from
the phase currents. Naturally, in this case also, all three phase currents from three cur-
rent transformers connected in a star arrangement must be available and connected.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...