Normally, the breaker failure protection evaluates the current flow criteri-
on as well as the position of the breaker auxiliary contact(s). If the auxil-
iary contact(s) status is not available in the device, this criterion cannot
be processed. In this case, set address
3909
Chk BRK CONTACT
to
No
.
The breaker failure protection in the 7SA6 can be operated single-stage
or two-stage:
Two-stage Breaker
Failure Protection
With two-stage operation, the trip command is repeated after a time delay
T1 to the local feeder breaker, normally to a different set of trip coils of
this breaker. A choice can be made whether this trip repetition shall be
single-pole or three-pole if the initial feeder protection trip was single-pole
(provided single-pole trip is possible). This choice is made in address
3903
1p-RETRIP (T1)
. Set this parameter to
Yes
if you wish single-
pole trip for the first stage, otherwise to
No
.
If the breaker does not respond to this first stage trip, the adjacent circuit
breakers must be tripped provided the fault has not yet been cleared. The
adjacent breakers are those of the other feeders on the bus-bar or bus-
bar section and — if signal transmission is possible — the breaker at the
remote end(s) of the protected object.
In the 7SA6, after a further delay time
T2
(address
3906
), the adjacent
circuit breakers (i.e. the breakers of the bus-bar zone and — if signal
transmission is possible — the breaker at the remote end) are tripped
provided the fault has not yet been cleared. An example of the time se-
quence is illustrated in Figure 6-136.
Separate delay times can be set:
−
for single- or three-pole trip repetition to the local feeder circuit breaker
after 1-pole trip of the feeder protection under address
3904
T1-
1pole
,
−
for three-pole trip repetition to the local feeder circuit breaker after 3-
pole trip of the feeder protection under address
3905
T1-3pole
,
−
for trip of the adjacent circuit breakers (bus-bar zone and remote end
if applicable) under address
3906
T2
.
The delay times are set dependant on the maximum operating time of the
feeder circuit breaker and the reset time of the current detectors of the
breaker failure protection, plus a safety margin which allows for any tol-
erance of the delay timers. The time sequence is illustrated in Figure 6-
136. For sinusoidal currents one can assume that the reset time of the
current detectors is less than 12 ms but if current transformer saturation
is expected then 25 ms should be assumed.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...