Appendix
B-8
7SA6 Manual
C53000-G1176-C156-2
1325
T3 DELAY
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec;
∞
0.60 sec
T3 delay
1331
Op. mode Z4
Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Non-Directional
Operating mode Z4
1332
R(Z4) Ø-Ø
Distance zones
(quadrilateral)
0.050..250.000 Ohm
12.000 Ohm
R(Z4), Resistance for ph-ph-faults
1333
X(Z4)
Distance zones
(quadrilateral)
0.050..250.000 Ohm
12.000 Ohm
X(Z4), Reactance
1334
RE(Z4) Ø-E
Distance zones
(quadrilateral)
0.050..250.000 Ohm
12.000 Ohm
RE(Z4), Resistance for ph-e faults
1335
T4 DELAY
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec;
∞
0.90 sec
T4 delay
1341
Op. mode Z5
Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode Z5
1342
R(Z5) Ø-Ø
Distance zones
(quadrilateral)
0.050..250.000 Ohm
12.000 Ohm
R(Z5), Resistance for ph-ph-faults
1343
X(Z5)+
Distance zones
(quadrilateral)
0.050..250.000 Ohm
12.000 Ohm
X(Z5)+, Reactance for Forward direc-
tion
1344
RE(Z5) Ø-E
Distance zones
(quadrilateral)
0.050..250.000 Ohm
12.000 Ohm
RE(Z5), Resistance for ph-e faults
1345
T5 DELAY
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec;
∞
0.90 sec
T5 delay
1346
X(Z5)-
Distance zones
(quadrilateral)
0.050..250.000 Ohm
4.000 Ohm
X(Z5)-, Reactance for Reverse direc-
tion
1351
Op. mode Z1B
Distance zones
(quadrilateral)
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z1B (overrreach
zone)
1352
R(Z1B) Ø-Ø
Distance zones
(quadrilateral)
0.050..250.000 Ohm
1.500 Ohm
R(Z1B), Resistance for ph-ph-faults
1353
X(Z1B)
Distance zones
(quadrilateral)
0.050..250.000 Ohm
3.000 Ohm
X(Z1B), Reactance
1354
RE(Z1B) Ø-E
Distance zones
(quadrilateral)
0.050..250.000 Ohm
3.000 Ohm
RE(Z1B), Resistance for ph-e faults
1355
T1B-1phase
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec;
∞
0.00 sec
T1B-1phase, delay for single ph. faults
1356
T1B-multi-phase
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec;
∞
0.00 sec
T1B-multi-ph, delay for multi ph. faults
1357
1st AR -> Z1B
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
NO
YES
YES
Z1B enabled before 1st AR (int. or ext.)
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...