Appendix
B-4
7SA6 Manual
C53000-G1176-C156-2
210
U4 transformer
Power System Data
1
not connected
Udelta transformer
Usync transformer
Ux reference transformer
not connected
U4 voltage transformer is
211
Uph / Udelta
Power System Data
1
0.10..9.99
1.73
Matching ratio Phase-VT To Open-
Delta-VT
212
Usync connect.
Power System Data
1
L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
L1-L2
VT connection for sync. voltage
214A
ϕ
Usync-Uline
Power System Data
1
0..360
°
0
°
Angle adjustment Usync-Uline
215
U-line / Usync
Power System Data
1
0.80..1.20
1.00
Matching ratio U-line / Usync
220
I4 transformer
Power System Data
1
not connected
Neutral Current (of the pro-
tected line)
Neutral Current of the paral-
lel line
Starpoint Curr. of earthed
power transf.
Neutral Current (of the pro-
tected line)
I4 current transformer is
221
I4/Iph CT
Power System Data
1
0.010..5.000
1.000
Matching ratio I4/Iph for CT's
230
Rated Frequency
Power System Data
1
50 Hz
60 Hz
50 Hz
Rated Frequency
235
PHASE SEQ.
Power System Data
1
L1 L2 L3
L1 L3 L2
L1 L2 L3
Phase Sequence
236
Distance Unit
Power System Data
1
km
Miles
km
Distance measurement unit
237
Format Z0/Z1
Power System Data
1
Zero seq. comp. factors RE/
RL and XE/XL
Zero seq. comp. factor K0
and angle(K0)
Zero seq. comp. factors RE/
RL and XE/XL
Setting format for zero seq.comp. for-
mat
239
T-CB close
Power System Data
1
0.01..0.60 sec
0.06 sec
Closing (operating) time of CB
240A
TMin TRIP CMD
Power System Data
1
0.02..30.00 sec
0.10 sec
Minimum TRIP Command Duration
241A
TMax CLOSE CMD Power System Data
1
0.01..30.00 sec
0.10 sec
Maximum Close Command Duration
242
T-CBtest-dead
Power System Data
1
0.00..30.00 sec
0.10 sec
Dead Time for CB test-autoreclosure
302
CHANGE
Change Group
Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A
Change to Another Setting Group
402A
WAVEFORMTRIG-
GER
Oscillographic Fault
Records
Save with Pickup
Save with TRIP
Start with TRIP
Save with Pickup
Waveform Capture
403A
WAVEFORM DATA Oscillographic Fault
Records
Fault event
Power System fault
Fault event
Scope of Waveform Data
410
MAX. LENGTH
Oscillographic Fault
Records
0.30..5.00 sec
2.00 sec
Max. length of a Waveform Capture
Record
411
PRE. TRIG. TIME
Oscillographic Fault
Records
0.05..0.50 sec
0.25 sec
Captured Waveform Prior to Trigger
412
POST REC. TIME
Oscillographic Fault
Records
0.05..0.50 sec
0.10 sec
Captured Waveform after Event
415
BinIn CAPT.TIME
Oscillographic Fault
Records
0.10..5.00 sec;
∞
0.50 sec
Capture Time via Binary Input
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...