Functions
6-298
7SA6 Manual
C53000-G1176-C156-2
tripping. Only one of these alarms appears at a time. These alarms are also intended
for the trip command output to the circuit breaker.
Single-Pole
Tripping with
Two-Phase Faults
Single-pole tripping for two-phase faults is a special feature. If a phase-phase fault
without earth occurs in an earthed system, this fault can be cleared by single-pole trip
and automatic reclosure in one of the faulted phases, as the short-circuit path is inter-
rupted in this manner. The phase selected for tripping must be the same at both line
ends (and should be the same for the entire system).
By means of the setting parameter
Trip2phFlt
it is possible to select whether this
tripping is
1pole leading Ph
, i.e. single-pole tripping of the leading phase or
1pol.lagging Ph
, i.e. single-pole tripping of the lagging phase. The standard set-
ting is
3pole
tripping for two-phase faults (presetting).
Table 6-15 shows a summary of the conditions under which single-pole or three-pole
tripping results.
Table 6-15
Single and three pole tripping depending on the type of fault
Fault type
from protection
functions)
Parameter 1156
Trip2phFlt
Trip output signals
RelayTrip
1pL1
RelayTrip
1pL2
RelayTrip
1pL3
Relay TRIP
3ph.
L1
(irrelevant)
X
L2
(irrelevant)
X
L3
(irrelevant)
X
L1
E
(irrelevant)
X
L2
E
(irrelevant)
X
L3
E
(irrelevant)
X
L1
L2
3pole
X
L1
L2
1pole leading.Ph
X
L1
L2
1pole lagging.Ph
X
L2
L3
3pole
X
L2
L3
1pole leading.Ph
X
L2
L3
1pole lagging.Ph
X
L1
L3
3pole
X
L1
L3
1pole leading.Ph
X
L1
L3
1pole lagging.Ph
X
L1
L2
E
(irrelevant)
X
L2
L3
E
(irrelevant)
X
L1
L3
E
(irrelevant)
X
L1
L2
L3
(irrelevant)
X
L1
L2
L3
E
(irrelevant)
X
E
(irrelevant)
X
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...