Technical Data
10-7
7SA6 Manual
C53000-G1176-C156
shielded data cable
– Test voltage
500 V; 50 Hz
– Transmission speed
min. 4800 Baud; max. 115200 Baud
factory setting: 38400 Baud
– Maximum transmission distance
max. 1km
Optical fibre
– Connector Type
ST–connector
for flush mounted case
rear panel, mounting location “C”
for surface mounted case
at the inclined housing on the case bottom
– Optical wavelength
λ
= 820 nm
– Laser class 1 acc. EN 60825–1/ –2
using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
– Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 µm
– Maximum transmission distance
1.5 km (0.93 miles)
– Character idle state
selectable; factory setting: “Light off”
System (SCADA)
Interface
(optional)
RS232/RS485/Optical
floating interface for data transfer
Profibus RS485/Profibus Optical
to a master terminal
acc. to ordered version
RS232
– Connection for flush mounted case
rear panel, mounting location “B”
9-pin DSUB socket
for surface mounted case
at the inclined housing on the case bottom
9-pin DSUB socket
– Test voltage
500 V; 50 Hz
– Transmission speed
min. 4800 Bd, max. 38400 Bd
factory setting: 19200 Bd
– Maximum transmission distance
15 m (50 ft)
RS485
– Connection for flush mounted case
rear panel, mounting location “B”
9-pin DSUB socket
for surface mounted case
at the inclined housing on the case bottom
9-pin DSUB socket
– Test voltage
500 V, 50 Hz
– Transmission speed
min. 4800 Bd, max. 38400 Bd
factory setting: 19200 Bd
– Maximum transmission distance
1000 m (3280 ft)
– Bridging distance
max. 1 km
Profibus RS485
– Connection for flush mounted case
rear panel, mounting location “B”
9-pin DSUB socket
for surface mounted case
at the inclined housing on the case bottom
9-pin DSUB socket
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...