Technical Data
10-3
7SA6 Manual
C53000-G1176-C156
Permissible AC ripple voltage,
Peak to peak
≤
15 % of nominal power supply
Power consumption
– quiescient
approx. 5 W
– energized
with 7SA610
∗
–
∗
A/E/J
approx. 8 W
with 7SA610
∗
–
∗
B/F/K
approx. 7 W
with 7SA6
∗
1
∗
–
∗
A/E/J/M/N/P approx. 14 W
with 7SA6
∗
1
∗
–
∗
B/F/K
approx. 12 W
with 7SA6
∗
2
∗
–
∗
A/E/J/M/P/R approx. 15 W
with 7SA613
∗
–
∗
A/M
approx. 15 W
with 7SA6
∗
2
∗
–
∗
B/K/F/N/Q/S approx. 20 W
with 7SA6
∗
2
∗
–
∗
C/G/L
approx. 16 W
plus approx. 1.5 W per interface module
Bridging time for failure/short-circuit
≥
50 ms at
U
NDC
= 48 V and
U
NDC
≥
110 V
of the power supply
≥
20 ms at
U
NDC
= 24 V and
U
NDC
= 60 V
Alternating Voltage
Voltage supply via integrated AC/DC converter
Power consumption
– quiescient
approx. 7 VA
– energized
with 7SA610
∗
–
∗
A/E/J
approx. 14 VA
with 7SA610
∗
–
∗
B/F/K
approx. 12 VA
with 7SA6
∗
1
∗
–
∗
A/E/J/M/N/P approx. 17 VA
with 7SA6
∗
1
∗
–
∗
B/F/K
approx. 17 VA
with 7SA6
∗
2
∗
–
∗
A/E/J/M/P/R approx. 20 VA
with 7SA613
∗
–
∗
A/M
approx. 20 VA
with 7SA6
∗
2
∗
–
∗
B/K/F/N/Q/S approx. 23 VA
with 7SA6
∗
2
∗
–
∗
C/G/L
approx. 21 VA
plus approx. 1.5 VA per interface module
Bridging time for failure/short-circuit
≥
50 ms
of the power supply
10.1.3 Binary Inputs and Outputs
Binary Inputs
Quantity
- 7SA610
∗
–
∗
A/E/J
5 (allocatable)
- 7SA610
∗
–
∗
B/F/K
7 (allocatable)
- 7SA61/31
∗
–
∗
A/E/J/M/N/P
13(allocatable)
- 7SA61/31
∗
–
∗
B/F/K
20(allocatable)
- 7SA61/32
∗
–
∗
A/E/J/M/P/R
21(allocatable)
- 7SA61/32
∗
–
∗
B/F/K/N/Q/S
29(allocatable)
- 7SA61/32
∗
–
∗
C/G/L
33(allocatable)
- 7SA613
∗
–
∗
A/M
21(allocatable)
Nominal power supply alternating voltage U
N AC
115 VAC
Permissible voltage ranges
92 to 132 VAC
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...