Functions
6-7
7SA6 Manual
C53000-G1176-C156-2
6.1.1
Power System Data 1
Some system and plant data are required by the device, so that it may adapt its func-
tions to these data, according to its mode of operation. Amongst others, the plant and
instrument transformer ratings, polarity and termination of the measured values, pa-
rameters of the circuit breaker, etc. These data are summarized in
Power System
Data 1 (P.System Data 1)
.
If the key
is operated, the main menu is displayed. With the key
the option
Set-
tings
is selected and by pushing the key
the selection of
Settings
is con-
firmed. To enter the plant data
Power System Data 1 (P.System Data 1)
must
be selected in the menu
Settings
.
With DIGSI
®
4 the corresponding selection is reached by double click on
Settings
.
Polarity of Current
Transformers
In address
201
CT Starpoint
the polarity of the current transformers must be en-
tered, in other words, the location of the CT star-point (Figure 6-8). This setting deter-
mines the measuring direction of the device (forward = line direction). A change of this
parameter also results in the polarity reversal of the earth current input.
Figure 6-8
Current transformer polarity
Instrument
Transformer
Nominal Values
In the address
203
Unom PRIMARY
and
204
Unom SECONDARY
the device is in-
formed of the primary and secondary rated voltage (line voltage) of the voltage trans-
formers. In the address
205
CT PRIMARY
and
206
CT SECONDARY
the primary and
secondary rated current (phase current) of the current transformers are entered.
Please observe that the rated current transformer secondary current must corre-
sponds to the rated current of the device, as the device would otherwise compute in-
correct primary data.
Correct entry of the primary data is a prerequisite for the correct computation of oper-
ational measured values with primary magnitude. If DIGSI
®
4 is used to enter param-
eters as primary quantities, the correct entry of the primary data is an important pre-
requisite for the correct operation of the device.
Voltage
Transformer
Connection
The device contains four voltage measuring inputs, three of which are connected to
the set of voltage transformers. For the fourth voltage transformer U
4
input several op-
tions are available:
•
Connection of the U
4
input to the open delta connection e–n of a set of voltage
transformers, refer also to Appendix A, Figures A-41 to A-45:
Address
210
is then set to:
U4 transformer
=
Udelta transf.
.
MENU
I
L1
I
L2
I
L3
I
N
I
L1
I
L2
I
L3
I
N
Bus
Address 0201 =
towards Line
Line
Line
Address 0201 =
towards Busbar
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...