Functions
6-211
7SA6 Manual
C53000-G1176-C156-2
Address
3466
2.AR Tdead 3Flt
; dead time after 3-phase starting
Address
3467
2.AR Tdead1Trip
; dead time after 1-pole tripping
Address
3468
2.AR Tdead3Trip
; dead time after 3-pole tripping
Address
3469
2.AR: Tdead EV.
; dead time in case of sequential fault
Address
3470
2.AR: CB? CLOSE
; check CB ready before reclosure
Address
3471
2.AR SynRequest
; sync. check after 3-pole tripping
For the 3rd cycle:
Address
3472
3.AR: START
; determines if starting in 3rd cycle is allowed at all
Address
3473
3.AR: T-ACTION
; action time for the 3rd cycle
Address
3475
3.AR Tdead 1Flt
; dead time after 1-phase starting
Address
3476
3.AR Tdead 2Flt
; dead time after 2-phase starting
Address
3477
3.AR Tdead 3Flt
; dead time after 3-phase starting
Address
3478
3.AR Tdead1Trip
; dead time after 1-pole tripping
Address
3479
3.AR Tdead3Trip
; dead time after 3-pole tripping
Address
3480
3.AR: Tdead EV.
; dead time in case of sequential fault
Address
3481
3.AR: CB? CLOSE
; check CB ready before reclosure
Address
3482
3.AR SynRequest
; sync. check after 3-pole tripping
For the 4th cycle:
Address
3483
4.AR: START
; determines if starting in 4th cycle is allowed at all
Address
3484
4.AR: T-ACTION
; action time for the 4th cycle
Address
3486
4.AR Tdead 1Flt
; dead time after 1-phase starting
Address
3487
4.AR Tdead 2Flt
; dead time after 2-phase starting
Address
3488
4.AR Tdead 3Flt
; dead time after 3-phase starting
Address
3489
4.AR Tdead1Trip
; dead time after 1-pole tripping
Address
3490
4.AR Tdead3Trip
; dead time after 3-pole tripping
Address
3491
4.AR: Tdead EV.
; dead time in case of sequential fault
Address
3492
4.AR: CB? CLOSE
; check CB ready before reclosure
Address
3493
4.AR SynRequest
; sync. check after 3-pole tripping
5th to 8th
reclosure cycles
If more than 4 cycles have been selected during the configuration of the scope of func-
tions (section 5.1), the cycles following the fourth cycle operate with the same settings
as the fourth cycle.
6.14.3 Settings
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in “Additional Settings“.
Addr.
Setting Title
Setting Options
Default Setting
Comments
3401
AUTO RECLOSE
OFF
ON
ON
Auto-Reclose function
3402
CB? 1.TRIP
YES
NO
NO
CB ready interrogation at 1st trip
3403
T-RECLAIM
0.50..300.00 sec
3.00 sec
Reclaim time after successful
AR cycle
3404
T-BLOCK MC
0.50..300.00 sec; 0
1.00 sec
AR blocking duration after
manual close
3406
EV. FLT. RECOG.
with Pickup
with Trip
with Trip
Evolving fault recognition
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...