Functions
6-319
7SA6 Manual
C53000-G1176-C156-2
−
Status information commands for setting / deactivating the “information status” for
the information value of an object:
−
Controlling activation of binary input status
−
Blocking binary outputs
6.24.2 Steps in the Command Sequence
Safety mechanisms in the command sequence ensure that a command can only be
released after a thorough check of preset criteria has been successfully concluded.
Additionally, user-defined interlocking conditions can be configured separately for
each device. The actual execution of the command is also monitored afterwards. The
entire sequence of a command is described briefly in the following:
Check Sequence
•
Command entry (e.g. using the keypad on the local user interface of the device)
−
Check password
→
access rights
−
Check switching mode (interlocking activated/deactivated)
→
selection of deac-
tivated interlocking status
•
User configurable interlocking checks that can be selected for each command
−
Switching authority (local, remote)
−
Switching direction control (target state = present state)
−
Zone controlled/bay interlocking (logic using CFC)
−
System interlocking (centrally via SICAM)
−
Double operation (interlocking against parallel switching operation)
−
Protection blocking (blocking of switching operations by protective functions)
•
Fixed commands
−
Timeout monitoring (time between command initiation and the beginning of the
execution can be controlled).
−
Configuration in process (if setting modification is in process, commands are re-
jected or delayed)
−
Equipment not present at output (if controllable equipment is not assigned to a
binary output, then the command is denied)
−
Output block (if an output block has been programmed for the circuit breaker, and
is active at the moment the command is processed, then the command is denied)
−
Component hardware malfunction
−
Command in progress (only one command can be processed at a time for each
circuit breaker or switch)
−
1- out of -n-check (for schemes with multiple assignments, such as common
ground, it is checked whether a command has already been initiated for the af-
fected output relay).
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...