Installation and Commissioning
8-44
7SA6 Manual
C53000-G1176-C156-2
8.2.2
Checking the Protection Data Communication
If the device features protection data interfaces for digital communication links, the
transmission way must be checked. The protection data communication is conducted
either directly from device to device via optical fibres or via communication converters
and a communication network or a dedicated transmission medium.
Optical fibres
The direct optical fibre connection is visually controlled by means of an optical fibre
connector. There is one connection for each direction. Therefore the output of the one
device must be connected to the input of the other device and vice versa. Transmis-
sion and receiving connections are identified with the symbols
for transmit
and
for receive. The visual check of the assignment of the transmission and
receive channels is relevant.
If using more than one device, the connections of all protection data interfaces are
checked according to the topology selected.
Communication
converter
Optical fibres are usually used for the connections between the devices and commu-
nication converters. The optical fibres such as the optical fibre direct connections are
checked. This is carried out for each protection data interface.
Set address
4502
CONNEC. 1 OVER
(see also Section 6.4.2) to configure the correct
type of connection.
Further
connections
For further connections a visual control is sufficient for the time being. Electrical and
functional controls are done during commissioning (Section 8.3.5).
Warning!
Do not look directly into the LEDs ! Laser class 3A according to EN 60825–1.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...