Technical Data
10-29
7SA6 Manual
C53000-G1176-C156
10.8
Protection Data Interface and Distance Protection Topology
(optional)
Protection Data
Interfaces
Number
1
– Connection optical fibre
mounting position “D”
for flush mounted case
on the rear side
for surface mounted case
at the inclined housing on the case bottom
Connection modules for protection data interface(s), depending on the ordering ver-
sion:
1
) Laser class 1 according to EN 60825–1/ –2 using glass fibre 62.5/125 µm
2
) Laser class 3A according to EN 60825–1/ –2
Character idle state
“Light off”
Protection Data
Communication
Direct connection:
Transmission speed
512 kbit/s
Type of fibre
Optical wavelength
Permissible path attenuation
Transmission distance
Connection via communication networks:
Communication converter
see Appendix A, Subsection
Accessories
Supported network interfaces
G703.1 with 64 kbits/s;
X21 with 64 or 128 or 512 kbit/s
Connection to communication converter see table above under
module FO5
Transmission speed
64 kbit/s with G703.1
512 kbit/s or 128 kBit/s or
64 kbit/s with X21
Max. transmission time
0.1 ms to 30 ms
(steps 0.1 ms)
Max. transmission time difference
0.000 ms to 3.000 ms
(steps 0.001 ms)
Transmission accuracy
CRC 32 according to CCITT or ITU
Module
in device
Type of
connector
Type of Fibre
Optical
wavelength
Perm. path
attenuation
Distance,
typical
FO5
1
)
ST
Multimode
62.5/125 µm
820 nm
8 dB
1.5 km
0.95 miles
FO6
2
)
ST
Multimode
62.5/125 µm
820 nm
16 dB
3.5 km
2.2 miles
FO7
2
)
ST
Monomode
9/125 µm
1300
nm
7 dB
10 km
6.25 miles
FO8
2
)
FC
Monomode
9/125 µm
1300
nm
18 dB
35 km
22 miles
refer table above
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...